Incident affecting Google Cloud Networking
Google Cloud Networking experiencing elevated latency in multiple regions
Incident began at 2023-03-29 14:37 and ended at 2023-03-30 16:06 (all times are US/Pacific).
Previously affected location(s)
Taiwan (asia-east1)Hong Kong (asia-east2)Tokyo (asia-northeast1)Osaka (asia-northeast2)Seoul (asia-northeast3)Mumbai (asia-south1)Delhi (asia-south2)Singapore (asia-southeast1)Jakarta (asia-southeast2)Sydney (australia-southeast1)Melbourne (australia-southeast2)Warsaw (europe-central2)Finland (europe-north1)Madrid (europe-southwest1)Belgium (europe-west1)Turin (europe-west12)London (europe-west2)Frankfurt (europe-west3)Netherlands (europe-west4)Zurich (europe-west6)Milan (europe-west8)Paris (europe-west9)GlobalTel Aviv (me-west1)Montréal (northamerica-northeast1)Toronto (northamerica-northeast2)São Paulo (southamerica-east1)Santiago (southamerica-west1)Iowa (us-central1)South Carolina (us-east1)Northern Virginia (us-east4)Columbus (us-east5)Dallas (us-south1)Oregon (us-west1)Los Angeles (us-west2)Salt Lake City (us-west3)Las Vegas (us-west4)
| Date | Time | Description | |
|---|---|---|---|
| | 30 Mar 2023 | 16:32 PDT | The issue related to latency for Google Cloud Networking is still ongoing and the latest updates for the same can be found here : https://status.cloud.google.com/incidents/NWHmzRntXN6AeNzjTFHV We apologize to all who are affected by the disruption. |
| | 30 Mar 2023 | 16:06 PDT | The issue with Google Cloud Networking has been resolved for all affected users as of Thursday, 2023-03-30 16:06 US/Pacific. We thank you for your patience while we worked on resolving the issue. |
| | 30 Mar 2023 | 14:23 PDT | Summary: Google Cloud Networking experiencing elevated latency in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any impact due to packet loss. However, we have identified an increase in latency for Google Cloud Networking affecting some regions, in particular us-central1, us-east4 and us-east5, due to physical damage resulting in a longer inter-regional path. We are continuing to work on recovering capacity as soon as possible by our onsite teams at the highest priority. We do not have an ETA for service restoration. We will provide an update by Thursday, 2023-03-30 16:00 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific on Wednesday, 2023-03-29. Customers may experience slightly elevated latency between regions while traffic recovers. Workaround: None at this time. |
| | 30 Mar 2023 | 11:41 PDT | Summary: Google Cloud Networking experiencing elevated latency in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any impact due to packet loss. However, we have identified an increase in latency for Google Cloud Networking affecting some regions, in particular us-central1, us-east4 and us-east5, due to physical damage resulting in reduced capacity and a longer inter-regional path. We are continuing to work on recovering capacity as soon as possible. We do not have an ETA for the mitigation at this point. We will provide an update by Thursday, 2023-03-30 14:00 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Customers may not see packet loss, however, will continue to observe latency while traffic recovers. Workaround: None at this time. |
| | 30 Mar 2023 | 09:53 PDT | Summary: Google Cloud Networking experiencing elevated latency in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any impact due to packet loss. However, we have identified an increase in latency affecting some regions, in particular us-central1, us-east4 and us-east5, due to physical damage resulting in reduced capacity and a longer inter-regional path. We are continuing to work on recovering capacity as soon as possible. We do not have an ETA for the mitigation at this point. We will provide an update by Thursday, 2023-03-30 12:00 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Customers may not see packet loss, however, will continue to observe latency while traffic recovers. Workaround: None at this time. |
| | 30 Mar 2023 | 08:02 PDT | Summary: Google Cloud Networking experiencing elevated latency in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any impact due to packet loss. However, we have identified an increase in latency affecting some regions, in particular us-central1, us-east4 and us-east5, due to physical damage resulting in reduced capacity and a longer inter-regional path. We are continuing to work on recovering capacity as soon as possible. We do not have an ETA for the mitigation at this point. We will provide an update by Thursday, 2023-03-30 10:00 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Customers may not see packet loss, however, will continue to observe latency while traffic recovers. Workaround: None at this time. |
| | 30 Mar 2023 | 05:47 PDT | Summary: Google Cloud Networking experiencing elevated latency in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any impact due to packet loss. However, we have identified an increase in latency affecting some regions, in particular us-central1 and us-east4, due to physical damage resulting in reduced capacity and a longer inter-regional path. We are continuing to work on recovering capacity as soon as possible. We do not have an ETA for the mitigation at this point. We will provide an update by Thursday, 2023-03-30 08:00 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Customers may not see packet loss, however, will continue to observe latency while traffic recovers. Workaround: None at this time. |
| | 30 Mar 2023 | 03:35 PDT | Summary: Google Cloud Networking experiencing elevated latency in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any impact due to packet loss. However, we have identified an increase in latency affecting some regions, in particular us-central1 and us-east4, due to physical damage resulting in reduced capacity and a longer inter-regional path. We are continuing to work on recovering capacity as soon as possible. We do not have an ETA for the mitigation at this point. We will provide an update by Thursday, 2023-03-30 06:00 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Customers may not see packet loss, however, will continue to observe latency while traffic recovers. Workaround: None at this time. |
| | 29 Mar 2023 | 22:24 PDT | Summary: Google Cloud Networking experiencing elevated latency in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any impact due to packet loss. However, we have identified an increase in latency affecting some regions, in particular us-central1 and us-east4, due to physical damage resulting in reduced capacity and a longer inter-regional path. We are working on recovering capacity as soon as possible. We do not have an ETA for the mitigation at this point. We will provide an update by Thursday, 2023-03-30 04:00 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Customers may not see packet loss, however, will continue to observe latency while traffic recovers. Workaround: None at this time. |
| | 29 Mar 2023 | 20:26 PDT | Summary: Google Cloud Networking experiencing elevated latency in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any impact due to packet loss. However, we have identified an increase in latency affecting some regions, in particular us-central1 and us-east4, due to physical damage resulting in reduced capacity and a longer inter-regional path. We are working on recovering capacity as soon as possible. We do not have an ETA for the mitigation at this point. We will provide an update by Thursday, 2023-03-30 01:00 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Customers may not see packet loss, however, will continue to observe latency while traffic recovers. Workaround: None at this time. |
| | 29 Mar 2023 | 19:38 PDT | Summary: Google Cloud Networking experiencing elevated latency in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any impact due to packet loss. However, we have identified an increase in latency affecting some regions, in particular us-central1 and us-east4, due to physical damage resulting in reduced capacity and a longer inter-regional path. We are working on recovering capacity as soon as possible. We do not have an ETA for the mitigation at this point. We will provide an update by Wednesday, 2023-03-29 20:30 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Customers may not see packet loss, however, will continue to observe latency while traffic recovers. Workaround: None at this time. |
| | 29 Mar 2023 | 18:29 PDT | Summary: Google Cloud Networking experiencing elevated latency in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any impact due to packet loss. However, we have identified an increase in latency affecting some regions, in particular us-central1 and us-east4, due to physical damage resulting in reduced capacity and a longer inter-regional path. We are working on recovering capacity as soon as possible. We do not have an ETA for the mitigation at this point. We will provide an update by Wednesday, 2023-03-29 20:00 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Customers may not see packet loss, however, will continue to observe latency while traffic recovers. Workaround: None at this time. |
| | 29 Mar 2023 | 17:40 PDT | Summary: Google Cloud Networking experiencing elevated latency in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any impact due to packet loss. However, we have identified an increase in latency affecting some regions, in particular us-central1 and us-east4, due to physical damage resulting in reduced capacity and a longer inter-regional path. We are working on recovering capacity as soon as possible. We will provide an update by Wednesday, 2023-03-29 18:10 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Customers may not see packet loss, however, will continue to observe latency while traffic recovers. Workaround: None at this time. |
| | 29 Mar 2023 | 17:39 PDT | Summary: Google Cloud Networking experiencing elevated latency in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any impact due to packet loss. However, we have identified an increase in latency affecting some regions, in particular us-central1 and us-east4, due to physical damage resulting in reduced capacity and a longer inter-regional path. We are working on recovering capacity as soon as possible. We will provide an update by Wednesday, 2023-03-29 18:10 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Workaround: None at this time. |
| | 29 Mar 2023 | 16:43 PDT | Summary: Google Cloud Networking experiencing elevated packet loss in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any packet loss or latency. Our engineers continue to further stabilize and prevent any recurrence. We will provide an update by Wednesday, 2023-03-29 17:40 US/Pacific with current details. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Workaround: None at this time. |
| | 29 Mar 2023 | 15:52 PDT | Summary: Google Cloud Networking experiencing elevated packet loss in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any packet loss or latency. We will provide an update by Wednesday, 2023-03-29 16:40 US/Pacific with current details. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Workaround: None at this time. |
| | 29 Mar 2023 | 15:36 PDT | Summary: Google Cloud Networking experiencing elevated packet loss in multiple regions Description: We believe the issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management is no longer causing any packet loss or latency. We will provide an update by Wednesday, 2023-03-29 16:13 US/Pacific with current details. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Workaround: None at this time. |
| | 29 Mar 2023 | 14:52 PDT | Summary: Google Cloud Networking experiencing elevated packet loss in multiple regions Description: We are experiencing an issue with Google Cloud Identity-Aware Proxy, Google Cloud Networking, Identity and Access Management. Our engineering team continues to investigate the issue. We will provide an update by Wednesday, 2023-03-29 15:26 US/Pacific with current details. We apologize to all who are affected by the disruption. Diagnosis: Customers experienced packet loss for two events in the approximate time frames 12:30 - 12:40 and 13:40 - 13:50 US/Pacific. Customers will continue to experience packet loss while traffic recovers. Workaround: None at this time. |