[{"id":"mSFVt6PiP557bjRyYsut","number":"2779651412601232975","begin":"2026-10-08T11:00:00+00:00","created":"2026-10-08T18:24:18+00:00","end":"2026-10-09T16:46:00+00:00","modified":"2026-10-14T07:24:12+00:00","external_desc":"Google Cloud Storage (GCS) customers experienced elevated latencies and error rates when performing upload or write operations.","updates":[{"created":"2026-10-14T07:15:32+00:00","modified":"2026-10-14T07:17:30+00:00","when":"2026-10-14T07:15:32+00:00","text":"## Incident Report\n## Date/Time of the Issue (All time US/Pacific)\n**Incident First Occurrence**\nIncident Start: 08 October 2026 04:00\nIncident End: 08 October 2026 16:30\nDuration: 12 hours, 30 minutes\n**Incident Recurrence**\nRecurrence Start: 09 October 2026 04:05\nRecurrence End: 09 October 2026 09:46\nDuration: 5 hours, 41 minutes\n**Total Duration:** 18 hours, 11 minutes\n## Summary\nOn Thursday, 08 October 2026, Google Cloud Storage experienced elevated write latency and write error rates while performing upload or write operations in the us-central1 region for a duration of 12 hours, 30 minutes. This was followed by a recurrence on Friday, 09 October 2026 in the us-central1-b zone for a duration of 5 hours, 41 minutes. We are taking immediate steps to ensure this doesn’t happen again.\n## Root Cause\nGoogle Cloud Storage relies on a highly distributed backend architecture to process and store incoming data. During the incident window, specific storage backend nodes within the us-central1 region experienced a localized capacity shortfall due to increased traffic.\nThe sequence of events leading to customer impact was as follows:\n* A traffic sorting optimization configuration update to the Google Cloud Storage load balancing layer intended to address localized capacity constraints caused severe resource exhaustion on specific storage backend nodes in the affected region by inadvertently bypassing the standard capacity-aware routing logic, resulting in a severe load imbalance.\n* Consequently, a small fraction of storage backend nodes in the us-central1 region received an overwhelming proportion of incoming write traffic despite having low available serving capacity. This concentration of traffic led to resource exhaustion on the affected backend servers causing backend services handling object data ingestion to begin timing out.\n* Because the underlying instances could not process the high volume of requests quickly enough, the incoming upload and write requests routed to these nodes experienced elevated latency and failed to complete, resulting in errors surfaced to customers.\n* Concurrently, a separate issue with the underlying database service contributed to additional metadata processing errors during a portion of the incident window.\n* The recurrence of the issue on October 9 was caused by an incomplete rollback of an upload planner feature, which broke the load balancing mechanism and overloaded a few smaller storage backend nodes.\n## Remediation and Prevention\nThe issue was initially detected on 08 October 2026 at 04:50 by Google engineering teams actively monitoring system telemetry early in the incident window. \nTo mitigate the issue, Google engineers executed the following step-by-step strategy:\n* Engineers initially attempted to dynamically allocate additional emergency capacity to the affected region, but this was blocked by systemic regional capacity limits.\n* To relieve immediate pressure, engineers selectively drained traffic from the most overloaded storage backend nodes.\n* A configuration change was deployed to disable the traffic sorting optimization, significantly reducing resource overhead on the storage backend.\n* For the concurrent metadata issue, engineers rolled back a recent update to the underlying metadata database service.\n* While these steps provided temporary relief, a recurrence of the load imbalance required further traffic redirection and draining of affected storage components. The incident was permanently resolved when engineering fully reverted the problematic load balancing configuration change, restoring the previous capacity-aware routing behavior and allowing traffic to distribute evenly across the region.\nOnce traffic levels stabilized and resource utilization returned to normal baseline levels, the previously drained nodes were restored to active service, successfully restoring normal operations.\n**Preventative Actions:**\nTo ensure this issue does not recur, we are implementing the following improvements:\n- **Safe Configuration Rollouts:** We are updating our deployment protocols to ensure that load balancing logic changes are rigorously validated in alternative, smaller regions before being rolled out to larger, highly utilized regions.\n- **Intelligent Operational Controls:** We are enhancing the storage load balancing architecture to strictly enforce capacity constraints, ensuring that traffic distribution logic cannot bypass pre-spilling safeguards and route traffic to clusters lacking sufficient serving resources.\n- **Resilient Scaling Logic:** We are implementing targeted improvements to accelerate internal data movement within highly utilized storage cells, enabling the system to process data more efficiently and handle temporary load spikes with greater resilience.\n## Description of Impact\nOn 08 October 2026, from 04:00 to 16:30 in us-central1 region and 09 October 2026, from 04:05 to 09:46 in us-central1-b zone, customers experienced elevated latency and error rates during Cloud Storage upload and write operations.\n* **Upload \u0026 Write Failures:** Customers primarily observed HTTP 503 UNAVAILABLE errors on WriteObject operations and client-side timeouts.\n* **Increased Write Latency:** Write operations that did succeed experienced significantly higher latencies than normal.\n* Cloud Storage operations in all other regions, as well as all other Google Cloud services, remained unaffected by this specific event.","status":"AVAILABLE","affected_locations":[]},{"created":"2026-10-09T16:44:56+00:00","modified":"2026-10-14T07:15:32+00:00","when":"2026-10-09T16:44:56+00:00","text":"## Preliminary Incident Report\nWe sincerely apologize for the disruption this incident caused to your business. We know how much you rely on Google Cloud, and we regret the impact on your productivity. We are working to address the root cause and prevent this from occurring in the future.\nPlease note, this information is based on our best knowledge at the time of posting and is subject to change as our investigation continues. A final Incident Report with preventative actions will be posted once our investigation is complete.\nIf you have experienced impact outside of what is listed below, please reach out to Google Cloud Support using [https\\://cloud.google.com/support](https://cloud.google.com/support)\n## Date/Time of the Issue (All time US/Pacific)\nIncident Start: 08 October 2026 04:00\nIncident End: 08 October 2026 16:30\nDuration: 12 hours, 30 minutes\n## Summary\nOn Thursday, 08 October 2026, Google Cloud Storage experienced elevated write latency and write error rates in the us-central1 region for a duration of 12 hours, 30 minutes. We are taking immediate steps to ensure this doesn’t happen again.\n## Preliminary Root Cause\nGoogle Cloud Storage relies on a highly distributed backend architecture to process and store incoming data. During the incident window, specific storage backend nodes within the us-central1 region experienced a localized capacity shortfall.\nThe sequence of events leading to customer impact was as follows:\n* A traffic sorting optimization intended to address localized capacity constraints caused severe resource exhaustion on specific backend storage nodes in the affected region.\n* This resource exhaustion caused backend services handling object data ingestion to begin timing out.\n* As a result, incoming upload and write requests routed to these nodes experienced elevated latency and failed to complete, resulting in errors surfaced to customers.\n* Concurrently, a separate issue with the underlying database service contributed to additional metadata processing errors during a portion of the incident window.\nGoogle engineers have begun a full root cause analysis (RCA) and will provide additional information once it is available.\n## Remediation\nThe issue was initially detected by Google engineering teams actively monitoring system telemetry early in the incident window.\nTo mitigate the issue, Google engineers executed the following step-by-step strategy:\n* Engineers initially attempted to dynamically allocate additional emergency capacity to the affected region, but this was blocked by systemic regional capacity limits.\n* To relieve immediate pressure, engineers selectively drained traffic from the most overloaded backend storage nodes.\n* A configuration change was deployed to disable the traffic sorting optimization, significantly reducing resource overhead on the storage backend.\n* For the concurrent metadata issue, engineers rolled back a recent update to the underlying metadata database service.\nOnce traffic levels stabilized and resource utilization returned to normal baseline levels, the previously drained nodes were restored to active service, successfully restoring normal operations.\n## Description of Impact\nOn 08 October, 2026, from 04:00 to 16:30 US/Pacific, customers utilizing the us-central1 region experienced elevated latency and error rates during Cloud Storage upload and write operations.\n* Customers primarily observed HTTP 503 UNAVAILABLE errors on WriteObject operations and client-side timeouts.\n* A minor impact was also observed on read operations during this timeframe.\n* Cloud Storage operations in all other regions, as well as all other Google Cloud services, remained unaffected by this specific event.","status":"AVAILABLE","affected_locations":[]},{"created":"2026-10-08T20:48:22+00:00","modified":"2026-10-09T16:44:56+00:00","when":"2026-10-08T20:48:22+00:00","text":"**Summary**\nGoogle Cloud Storage customers are experiencing elevated latencies and error rates when performing upload or write operations\n**Description**\nWe are continuing to mitigate the issue with Google Cloud Storage in the us-central1 region that began on Thursday, 2026-10-08 05:19 PDT.\nThe initial mitigations applied by our engineering team continue to show observable improvements in error rates.\nOur engineering team is actively monitoring the environment and rolling out further mitigations to fully stabilize the service.\nWe will provide an update by Thursday, 2026-10-08 16:00 PDT with current details.\n**Customer Symptoms**\n* Customers are experiencing elevated latencies and error rates when performing upload or write operations.\n* A smaller subset of read operations may also experience increased latency and errors\n**Workaround**\nNone at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Iowa (us-central1)","id":"us-central1"}]},{"created":"2026-10-08T19:38:18+00:00","modified":"2026-10-08T20:48:22+00:00","when":"2026-10-08T19:38:18+00:00","text":"**Summary**\nGoogle Cloud Storage customers are experiencing elevated latencies and error rates when performing upload or write operations\n**Description**\nWe are continuing to mitigate the issue with Google Cloud Storage in the us-central1 region that began on Thursday, 2026-10-08 05:19 PDT.\nThe initial mitigations applied by our engineering team continue to show observable improvements in error rates. Our engineering team is actively monitoring the environment and rolling out further mitigations to fully stabilize the service.\nWe will provide an update by Thursday, 2026-10-08 14:00 PDT with current details.\n**Customer Symptoms**\n* Customers are experiencing elevated latencies and error rates when performing upload or write operations.\n* A smaller subset of read operations may also experience increased latency and errors\n**Workaround**\nNone at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Iowa (us-central1)","id":"us-central1"}]},{"created":"2026-10-08T18:55:19+00:00","modified":"2026-10-08T19:38:18+00:00","when":"2026-10-08T18:55:19+00:00","text":"**Summary**\nGoogle Cloud Storage customers are experiencing elevated latencies and error rates when performing upload or write operations\n**Description**\nWe are experiencing an issue with Google Cloud Storage beginning on Thursday, 2026-10-08 05:19 PDT.\nInitial mitigations applied by our engineering team leading to observable improvements in error rates in our internal monitoring beginning 10:57 PDT. Work remains underway to roll out further mitigations.\nWe will provide an update by Thursday, 2026-10-08 12:45 PDT with current details.\n**Customer Symptoms**\n* Customers are experiencing elevated latencies and error rates when performing upload or write operations.\n* A smaller subset of read operations may also experience increased latency and errors\n**Workaround**\nNone at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Iowa (us-central1)","id":"us-central1"}]},{"created":"2026-10-08T18:34:00+00:00","modified":"2026-10-08T18:55:19+00:00","when":"2026-10-08T18:34:00+00:00","text":"**Summary**\nGoogle Cloud Storage customers are experiencing elevated latencies and error rates when performing upload or write operations\n**Description**\nWe are experiencing an issue with Google Cloud Storage beginning on Thursday, 2026-10-08 05:19 PDT.\nInitial mitigations applied by our engineering team leading to observable improvements in error rates in our internal monitoring. Work remains underway to roll out further mitigations.\nWe will provide an update by Thursday, 2026-10-08 12:00 PDT with current details.\n**Customer Symptoms**\n* Customers are experiencing elevated latencies and error rates when performing upload or write operations.\n* A smaller subset of read operations may also experience increased latency and errors\n**Workaround**\nNone at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Iowa (us-central1)","id":"us-central1"}]},{"created":"2026-10-08T18:24:18+00:00","modified":"2026-10-08T18:34:00+00:00","when":"2026-10-08T18:24:18+00:00","text":"**Summary**\nGoogle Cloud Storage customers are experiencing elevated latencies and error rates when performing upload or write operations\n**Description**\nWe are experiencing an issue with Google Cloud Storage beginning on Thursday, 2026-10-08 05:19 PDT.\nOur engineering team continues to investigate the issue.\nWe will provide an update by Thursday, 2026-10-08 11:50 PDT with current details.\n**Customer Symptoms**\n* Customers are experiencing elevated latencies and error rates when performing upload or write operations.\n* A smaller subset of read operations may also experience increased latency and errors\n**Workaround**\nNone at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Iowa (us-central1)","id":"us-central1"}]}],"most_recent_update":{"created":"2026-10-14T07:15:32+00:00","modified":"2026-10-14T07:17:30+00:00","when":"2026-10-14T07:15:32+00:00","text":"## Incident Report\n## Date/Time of the Issue (All time US/Pacific)\n**Incident First Occurrence**\nIncident Start: 08 October 2026 04:00\nIncident End: 08 October 2026 16:30\nDuration: 12 hours, 30 minutes\n**Incident Recurrence**\nRecurrence Start: 09 October 2026 04:05\nRecurrence End: 09 October 2026 09:46\nDuration: 5 hours, 41 minutes\n**Total Duration:** 18 hours, 11 minutes\n## Summary\nOn Thursday, 08 October 2026, Google Cloud Storage experienced elevated write latency and write error rates while performing upload or write operations in the us-central1 region for a duration of 12 hours, 30 minutes. This was followed by a recurrence on Friday, 09 October 2026 in the us-central1-b zone for a duration of 5 hours, 41 minutes. We are taking immediate steps to ensure this doesn’t happen again.\n## Root Cause\nGoogle Cloud Storage relies on a highly distributed backend architecture to process and store incoming data. During the incident window, specific storage backend nodes within the us-central1 region experienced a localized capacity shortfall due to increased traffic.\nThe sequence of events leading to customer impact was as follows:\n* A traffic sorting optimization configuration update to the Google Cloud Storage load balancing layer intended to address localized capacity constraints caused severe resource exhaustion on specific storage backend nodes in the affected region by inadvertently bypassing the standard capacity-aware routing logic, resulting in a severe load imbalance.\n* Consequently, a small fraction of storage backend nodes in the us-central1 region received an overwhelming proportion of incoming write traffic despite having low available serving capacity. This concentration of traffic led to resource exhaustion on the affected backend servers causing backend services handling object data ingestion to begin timing out.\n* Because the underlying instances could not process the high volume of requests quickly enough, the incoming upload and write requests routed to these nodes experienced elevated latency and failed to complete, resulting in errors surfaced to customers.\n* Concurrently, a separate issue with the underlying database service contributed to additional metadata processing errors during a portion of the incident window.\n* The recurrence of the issue on October 9 was caused by an incomplete rollback of an upload planner feature, which broke the load balancing mechanism and overloaded a few smaller storage backend nodes.\n## Remediation and Prevention\nThe issue was initially detected on 08 October 2026 at 04:50 by Google engineering teams actively monitoring system telemetry early in the incident window. \nTo mitigate the issue, Google engineers executed the following step-by-step strategy:\n* Engineers initially attempted to dynamically allocate additional emergency capacity to the affected region, but this was blocked by systemic regional capacity limits.\n* To relieve immediate pressure, engineers selectively drained traffic from the most overloaded storage backend nodes.\n* A configuration change was deployed to disable the traffic sorting optimization, significantly reducing resource overhead on the storage backend.\n* For the concurrent metadata issue, engineers rolled back a recent update to the underlying metadata database service.\n* While these steps provided temporary relief, a recurrence of the load imbalance required further traffic redirection and draining of affected storage components. The incident was permanently resolved when engineering fully reverted the problematic load balancing configuration change, restoring the previous capacity-aware routing behavior and allowing traffic to distribute evenly across the region.\nOnce traffic levels stabilized and resource utilization returned to normal baseline levels, the previously drained nodes were restored to active service, successfully restoring normal operations.\n**Preventative Actions:**\nTo ensure this issue does not recur, we are implementing the following improvements:\n- **Safe Configuration Rollouts:** We are updating our deployment protocols to ensure that load balancing logic changes are rigorously validated in alternative, smaller regions before being rolled out to larger, highly utilized regions.\n- **Intelligent Operational Controls:** We are enhancing the storage load balancing architecture to strictly enforce capacity constraints, ensuring that traffic distribution logic cannot bypass pre-spilling safeguards and route traffic to clusters lacking sufficient serving resources.\n- **Resilient Scaling Logic:** We are implementing targeted improvements to accelerate internal data movement within highly utilized storage cells, enabling the system to process data more efficiently and handle temporary load spikes with greater resilience.\n## Description of Impact\nOn 08 October 2026, from 04:00 to 16:30 in us-central1 region and 09 October 2026, from 04:05 to 09:46 in us-central1-b zone, customers experienced elevated latency and error rates during Cloud Storage upload and write operations.\n* **Upload \u0026 Write Failures:** Customers primarily observed HTTP 503 UNAVAILABLE errors on WriteObject operations and client-side timeouts.\n* **Increased Write Latency:** Write operations that did succeed experienced significantly higher latencies than normal.\n* Cloud Storage operations in all other regions, as well as all other Google Cloud services, remained unaffected by this specific event.","status":"AVAILABLE","affected_locations":[]},"status_impact":"SERVICE_DISRUPTION","severity":"medium","service_key":"UwaYoXQ5bHYHG6EdiPB8","service_name":"Google Cloud Storage","affected_products":[{"title":"Google Cloud Storage","id":"UwaYoXQ5bHYHG6EdiPB8","current_title":"Google Cloud Storage"}],"uri":"incidents/mSFVt6PiP557bjRyYsut","currently_affected_locations":[],"previously_affected_locations":[{"title":"Iowa (us-central1)","id":"us-central1"}]},{"id":"J5ia5t9p3g9Q5Wi7r8Ev","number":"847028556969787721","begin":"2026-09-01T14:42:00+00:00","created":"2026-09-01T16:03:12+00:00","end":"2026-09-01T18:52:00+00:00","modified":"2026-10-17T21:49:14+00:00","external_desc":"Multiple products in us-central1-b are experiencing network service degradation.","updates":[{"created":"2026-09-29T16:09:46+00:00","modified":"2026-10-17T21:49:14+00:00","when":"2026-09-29T16:09:46+00:00","text":"## Addendum to Incident Report\nThis addendum extends the Detailed Description of Impact from the previous message. Though only two clusters in a datacenter in us-central1-b and us-central1-f experienced network isolation, a few regional products with a dependency on the affected datacenter were also affected. Between 07:41 and 11:52 US/Pacific on Tuesday, September 1, 2026, the following products were affected:\n- **Compute Engine VMs**: VMs running in the affected data center lost network connectivity to resources located outside of their datacenter. From a Compute Engine perspective, this incident only affected a subset of VMs in us-central1-b and us-central1-f.\n- **Zonal and Regional Products Based on Compute Engine** Products with dependencies on VMs in the affected datacenter experienced symptoms like connection timeouts or service unavailability because the underlying VMs lost network connectivity.\nExamples of products that are based on Compute Engine VMs include: Apigee, Cloud SQL, AlloyDB for PostgreSQL, Dataflow, Cloud Filestore, and Looker.\n- **Google Kubernetes Engine (GKE)**: GKE clusters whose control plane had dependencies on Compute Engine VMs in the affected clusters experienced errors and timeouts when administrators or nodes attempted to connect to the Kubernetes API server. Consequently, deployments might have been delayed, Kubernetes API operations might have failed, and new nodes might not have registered with the control plane (causing node pool operational delays).\n- **Cloud Run and App Engine:** Workloads in the us-central1 region experienced elevated serving latency, 5xx aborted request errors, and outbound connectivity degradation. To prevent severe request failures, traffic was diverted to other clusters. Diverting requests to other clusters temporarily caused elevated latency or errors in those clusters.Once the impacted cluster was restored, workload demand for these new backends created a 'thundering herd' of concurrent instance initializations. This sudden surge bypassed warm caches and overwhelmed internal file-serving tiers, extending symptoms until emergency capacity was provisioned.\n- **Other Google APIs and Services**, in us-central1 or a multi-region that includes us-central1, were affected if they had dependencies on software tasks in the affected clusters and weren't able to use software tasks in an unaffected cluster. Symptoms included connection timeouts or service unavailability. Examples of other Google APIs and services are: Google Cloud Bigtable, BigQuery, Google SecOps SOAR, Cloud Spanner, and Cloud Firestore. For some services, symptoms were limited to temporary latency spikes and service unavailability until workloads shifted to unaffected clusters.\n- **Private Service Connect**: Clients (in any region) experienced connectivity issues involving PSC endpoints with dependencies in us-central1, in specific circumstances: - PSC endpoints for Google APIs were affected in the same way as noted in the Google APIs and services section. - Producer/consumer PSC endpoints were affected if the producer had load balancers or backend VMs in the affected clusters of us-central1.\n- **Hybrid Connectivity**: Some Cloud Router, Cloud VPN, and Cloud Interconnect VLAN attachments in us-central1 were affected in specific circumstances: - Cloud Router BGP software tasks for some Cloud Routers in us-central1 experienced a Cloud Router maintenance event if their BGP software tasks were running in the affected clusters. - Cloud VPN tunnel software tasks running in the affected clusters lost network connectivity. This caused some Cloud VPN tunnels in us-central1 to go down until a replacement tunnel task in a different cluster was assigned. - Resources (in any region) sending packets through Cloud Interconnect VLAN attachments in us-central1 might have experienced intermittent connectivity issues in certain situations where network flows weren’t already programmed.\n- **Envoy-based load balancers and other products**: Load balancers and other products that depended on managed Envoy tasks of a proxy-only subnet in us-central1 experienced increased latency or connectivity issues if enough Envoy tasks were in the affected clusters. The following products were affected: - Regional external application load balancers in us-central1 - Regional internal application load balancers in us-central1 - Cross-region internal application load balancers with proxies in us-central1 - Regional external proxy network load balancers in us-central1 - Regional internal proxy network load balancers in us-central1 - Cross-region internal proxy network load balancers with proxies in us-central1 - Secure Web Proxy in us-central1","status":"AVAILABLE","affected_locations":[]},{"created":"2026-09-10T21:20:16+00:00","modified":"2026-09-29T16:09:46+00:00","when":"2026-09-10T21:20:16+00:00","text":"## Incident Report\n## Summary\nOn Tuesday, 1 September 2026, some customers in us-central1 experienced network service degradation and instance isolation for a duration of 4 hours and 11 minutes. To our customers whose businesses were impacted during this disruption, we sincerely apologize. This is not the level of quality and reliability we strive to offer you, and we are taking immediate steps to improve the platform’s performance and availability.\n## Root Cause\nThe event was triggered by the inadvertent physical disconnection of network fiber-optic cables during routine hardware maintenance. A technician was performing a scheduled capacity upgrade on data center routers that support a fraction of capacity in the us-central1-b zone and a small fraction of capacity in the us-central1-f zone.\nDuring the hands-on maintenance, optical fibers connecting the data center routers to the network fabric were unplugged and the optical transceivers were replaced with a transceiver that supports higher-density connectivity. This transceiver was not compatible with the transceivers still in place in the data center fabric, causing a loss of connectivity for each fiber.\nThe network is designed with redundant routers in separate data center rooms within the same building so that failure of one router does not interrupt service. The maintenance was intended to upgrade one router at a time over several days, with traffic diversions at each step and verification between steps that the network has returned to a fully-connected state.\nHowever, a procedural error in the manually orchestrated upgrade process caused the complete list of transceiver replacements across all routers to be issued to the technician without instructions to sequence the work one router at a time. The maintenance workflow also did not include the expected human and software verification steps for detecting unintended disruption.\nAs a result, the technician sequentially unplugged all fiber paths across the affected devices within 13 minutes. The speed and nature of the error prevented warnings of incorrect action from reaching the engineer before connectivity was lost. Additionally, a standing procedure to halt if light is detected on any fiber-optic cable after unplug was not followed.\nThis resulted in compute capacity in the impacted zone being isolated from the network. Customers were unable to reach their virtual machines, and those virtual machines could not establish connections outside their zone.\n## Remediation and Prevention\nThe issue was detected immediately by automated network loss monitoring systems as well as proactive probes, which rapidly engaged the network engineering and incident response teams.\nTo mitigate the immediate customer impact, engineering teams actively moved traffic away from the impacted infrastructure.\nConcurrently, hardware operations technicians on site identified the disconnected optical links and physically re-inserted the original optical transceivers. Once the physical links were fully restored, traffic flow rates normalized and the traffic was redirected back to return the capacity to service.\nGoogle is committed to preventing a repeat of this issue in the future and is completing the following actions:\n* Reinforce training in us-central1 region and globally around safe maintenance techniques, including the mandatory requirement to verify whether light is on every unplugged fiber.\n* Finish the migration of network upgrade workflows to a fully automatically sequenced orchestration system. Most common regional network workflows were completed in 2025, and zonal workflows are in progress.\n* Complete the deployment of work stop alerting for actions resulting in the unintended disconnection of live fiber cables in Google data centers.\n* Complete the deployment of the automated system that will move regional traffic away from faulty zones, reducing the time from approximately 19 minutes in this instance to around 5 minutes.\n## Detailed Description of Impact\nOn Tuesday, 1 September, from 07:41 to 11:52 US/Pacific, a portion of the us-central1-b and us-central1-f zones experienced severe network degradation and resource isolation.\n1. Multiple products affected: The network disruption to/from a portion of us-central1-b and us-central1-f zones impacted all zonal GCP Products for some customers in those zones.\n2. Regional impact: Regional products using capacity in the affected data center were affected until traffic diversions were fully in place at 08:00 US/Pacific. Google Kubernetes Engine and Cloud Run / Google App Engine had longer impacts, discussed below.\n3. Error rate: Traffic flow drop rates for resources hosted in the affected area reached 100% during the peak of the incident, resulting in unreachable virtual machines and elevated packet loss.\n**Affected Services and Features**\n* Google Compute Engine: Inability for users in the affected portion of us-central1-b and us-central1-f zones to access virtual machines externally, and inability for VMs to reach remote resources.\n* Cloud SQL, AlloyDB for PostgreSQL, Google Cloud Bigtable, Cloud Filestore: Data access and connectivity severed for instances localized strictly to the impacted infrastructure.\n* Cloud Spanner, Cloud Firestore: Elevated Remote Procedure Call (RPC) error rates, write timeouts, and latency spikes for the nam5 multi-region instances due to severed connectivity to components running in the impacted zone.\n* Virtual Private Cloud (VPC), Cloud NAT, Apigee, Google BigQuery, Google Cloud Dataflow, Looker, Google SecOps SOAR, Hybrid Connectivity, Cloud Interconnect: Elevated network packet loss, connectivity drops, and API timeouts in the impacted zone.\n* Google Kubernetes Engine (GKE): Between 07:40 and 09:15 US/Pacific on 2026-09-01, customers experienced errors and timeouts on requests to their GKE cluster control planes (Kubernetes API servers) in us-central1. This could have caused new or updated workloads to fail scheduling and Kubernetes API operations to fail.\n* Cloud Run / Google App Engine: Temporary latency spikes and pending queue aborts as backend workloads automatically evacuated and shifted to healthy capacity. A subset of workloads in the specifically impacted area experienced degradation until 11:52 US/Pacific.\n**Customer Impact**\nCustomers with resources hosted in the specific affected clusters within us-central1-b and us-central1-f experienced a complete loss of network connectivity starting at 07:41 US/Pacific.\nDuring this time, virtual machines and associated services became unreachable from the internet and from other Google Cloud regions, and those internal resources could not initiate outbound connections.\nThe issue was detected almost immediately and engineers took traffic diversion actions at 07:45 and 08:00 US/Pacific to reduce impact to regional products.\nBy 08:50 US/Pacific, the majority of physical connections were restored and traffic began recovering, and the traffic diversion actions were removed at 09:19 US/Pacific.\nFull recovery across nearly all affected services and long-running operations was confirmed by 11:52 US/Pacific.\nBecause the network isolation was strictly limited to specific clusters within us-central1-b and us-central1-f, multi-zonal deployments correctly utilizing redundancy across other zones in us-central1 were largely able to bypass the physical hardware failure and continue serving traffic.\nCustomers with projects in both us-central1-b and us-central1-f would not have seen multi-zonal impact - at most one of their zones would have capacity in the affected data center.","status":"AVAILABLE","affected_locations":[]},{"created":"2026-09-03T17:47:02+00:00","modified":"2026-09-10T21:20:16+00:00","when":"2026-09-03T17:47:02+00:00","text":"## Preliminary Incident Report\nWe sincerely apologize for the disruption this incident caused to your business. We know how much you rely on Google Cloud, and we regret the impact on your environment. We are working to address the root cause and prevent this from occurring in the future.\nPlease note, this information is based on our best knowledge at the time of posting and is subject to change as our investigation continues. A final Incident Report with preventative actions will be posted once our investigation is complete.\nIf you have experienced impact outside of what is listed below, please reach out to Google Cloud Support using https://cloud.google.com/support\n## Date/Time of the Issue (All time US/Pacific)\n**Incident Start**: 1 September 2026 07:41\n**Incident End**: 1 September 2026 11:52\n**Duration**: 4 hours, 11 minutes\n## Summary\nOn Tuesday, 1 September 2026, some customers in us-central1-b experienced network service degradation and instance isolation for a duration of 4 hours and 11 minutes. To our customers whose businesses were impacted during this disruption, we sincerely apologize. This is not the level of quality and reliability we strive to offer you, and we are taking immediate steps to improve the platform’s performance and availability.\n## Preliminary Root Cause\nThe immediate technical trigger for this event was the inadvertent physical disconnection of network fiber-optic cables during a routine hardware maintenance procedure. An engineer was performing a scheduled capacity upgrade on datacenter routers that support a fraction of capacity in the us-central1-b zone.\nThe network architecture for each datacenter is designed with redundancy across multiple routing devices. The system is designed to be resilient to all single device or fiber-path failures, and most double- or triple-failures do not affect customer traffic. To ensure this, the devices and fiber paths are physically separated in each datacenter, with diverse power sources.\nA procedural error meant that the physical maintenance action sequentially unplugged 100% of fiber paths across all devices within 13 minutes. The nature of the error, combined with the speed of the action, prevented warnings of incorrect action reaching the engineer before complete disconnection.\nThis resulted in compute capacity in the impacted zone being isolated from the network. Customers were unable to reach their virtual machines, and those virtual machines could not establish connections outside their zone.\n## Remediation\nThe issue was detected immediately by automated network loss monitoring systems as well as proactive probes, which rapidly engaged the network engineering and incident response teams.\nTo mitigate the immediate customer impact, engineering teams actively moved traffic away from the impacted infrastructure, automatically shifting compatible workload traffic to healthy capacity elsewhere in the region.\nConcurrently, hardware operations technicians on site identified the disconnected optical links and physically reseated the fibers. Once the physical links were fully restored, traffic flow rates normalized and the traffic was redirected back to return the capacity to service.\n## Description of Impact\nOn Tuesday, 1 September, from 07:41 to 11:52 US/Pacific, a portion of the us-central1-b zone experienced severe network degradation and resource isolation.\n* **Multiple products affected:** The network disruption to/from a portion of us-central1-b impacted multiple GCP Products for some customers in that zone.\n* **Error rate:** Traffic flow drop rates for resources hosted in the affected area reached 100% during the peak of the incident, resulting in unreachable virtual machines and elevated packet loss.\n**Affected Services and Features**\n* **Google Compute Engine:** Inability to access virtual machines externally, and inability for VMs to reach remote resources.\n* **Google Kubernetes Engine:** Unreachable regional/zonal clusters and nodes within the affected zone, prompting delayed cluster recovery times.\n* **Cloud Run / Google App Engine:** Temporary latency spikes and pending queue aborts as backend workloads automatically evacuated and shifted to healthy capacity. A subset of workloads in the specifically impacted area experienced degradation until 11:52 US/Pacific.\n* **Cloud SQL, AlloyDB for PostgreSQL, Cloud Spanner, Google Cloud Bigtable, Cloud Filestore:** Data access and connectivity severed for instances localized strictly to the impacted infrastructure.\n* **Virtual Private Cloud (VPC), Cloud NAT, Apigee, Google BigQuery, Google Cloud Dataflow, Looker, Google SecOps SOAR, Hybrid Connectivity, Cloud Interconnect:** Elevated network packet loss, connectivity drops, and API timeouts in the impacted zone.","status":"AVAILABLE","affected_locations":[]},{"created":"2026-09-01T19:12:28+00:00","modified":"2026-09-03T17:47:02+00:00","when":"2026-09-01T19:12:28+00:00","text":"**Summary**\nMultiple products in us-central1-b experienced network service degradation.\n**Description**\nThe issue was affecting a portion of the us-central1-b zone. The remaining zones in the region were unaffected.\nAll the impacted products have recovered.\nFrom preliminary analysis, routine network fabric path maintenance triggered unexpected issues in one cluster in us-central1-b. We have recovered the network capacity that was impacted and restored all zonal and regional services. Maintenance in the region has been halted while proactive audits are carried out.\nWe thank you for your patience while we worked on resolving the issue.\n**Customer Symptoms**\nCustomers experienced elevated packet loss and errors.\n**Workaround**\nThe issue has been mitigated.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Iowa (us-central1)","id":"us-central1"}]},{"created":"2026-09-01T18:36:56+00:00","modified":"2026-09-01T19:12:28+00:00","when":"2026-09-01T18:36:56+00:00","text":"**Summary**\nMultiple products in us-central1-b are experiencing network service degradation.\n**Description**\nThe issue is affecting a portion of the us-central1-b zone. The remaining zones in the region are unaffected.\nMost of the products have recovered. The impacted products Cloud Run and App Engine are also seeing recovery and the errors have lowered pre-incident levels. Engineering continues to monitor and validate.\nRoutine network fabric path maintenance triggered unexpected issues in two clusters in us-central1-b. We have recovered the network capacity that was impacted and restored all zonal and regional services. Maintenance in the region has been halted while proactive audits are carried out.\nWe will provide more information by Tuesday, 2026-09-01 12:30 US/Pacific with current details.\n**Customer Symptoms**\nCustomers are experiencing elevated packet loss and errors.\n* Cloud Run\n* App Engine\nFollowing products have recovered\n* BigQuery\n* Cloud Dataflow\n* Cloud Bigtable\n* Compute Engine\n* Cloud Hybrid Connectivity\n* Cloud Filestore\n* Virtual Private Cloud\n* Cloud Spanner\n* Google Kubernetes Engine\n* Cloud SQL\n* AlloyDBCloud VPN\n* Apigee\n* Cloud Interconnect\n* Cloud NAT\n* Looker (Google Cloud core)\n* Google SecOps SOAR\n* Cloud Firestore\n**Workaround**\n* Customers with service layer retries may see successful completions as only a portion of the zone is affected.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Iowa (us-central1)","id":"us-central1"}]},{"created":"2026-09-01T18:01:09+00:00","modified":"2026-09-01T18:36:56+00:00","when":"2026-09-01T18:01:09+00:00","text":"**Summary**\nMultiple products in us-central1-b are experiencing network service degradation.\n**Description**\nThe issue is affecting a portion of the us-central1-b zone. The remaining zones in the region are unaffected.\nMost of the products have recovered and the engineering team is still validating a few remaining product impacts.\nRoutine network maintenance triggered issues in us-central1-b. We have recovered the network capacity that was impacted and restored all zonal and regional services. Maintenance in the region has been halted while proactive audits are carried out.\nWe will provide more information by Tuesday, 2026-09-01 12:30 US/Pacific with current details.\n**Customer Symptoms**\nCustomers are experiencing elevated packet loss and errors.\n* Cloud Run\n* App Engine\nFollowing products have recovered\n* BigQuery\n* Cloud Dataflow\n* Cloud Bigtable\n* Compute Engine\n* Cloud Hybrid Connectivity\n* Cloud Filestore\n* Virtual Private Cloud\n* Cloud Spanner\n* Google Kubernetes Engine\n* Cloud SQL\n* AlloyDBCloud VPN\n* Apigee\n* Cloud Interconnect\n* Cloud NAT\n* Looker (Google Cloud core)\n* Google SecOps SOAR\n* Cloud Firestore\n**Workaround**\n* Customers with service layer retries may see successful completions as only a portion of the zone is affected.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Iowa (us-central1)","id":"us-central1"}]},{"created":"2026-09-01T17:09:04+00:00","modified":"2026-09-01T18:01:09+00:00","when":"2026-09-01T17:09:04+00:00","text":"**Summary**\nMultiple products in us-central1-b are experiencing network service degradation.\n**Description**\nThe issue is affecting a portion of the us-central1-b zone. The remaining zones in the region are unaffected.\nMost of the products have recovered and the engineering team is still validating a few remaining product impacts.\nWe will provide more information by Tuesday, 2026-09-01 11:00 US/Pacific with current details.\n**Customer Symptoms**\nCustomers are experiencing elevated packet loss and errors.\n* Cloud Run\n* App Engine\nFollowing products have recovered\n* BigQuery\n* Cloud Dataflow\n* Cloud Bigtable\n* Compute Engine\n* Cloud Hybrid Connectivity\n* Cloud Filestore\n* Virtual Private Cloud\n* Cloud Spanner\n* Google Kubernetes Engine\n* Cloud SQL\n* AlloyDBCloud VPN\n* Apigee\n* Cloud Interconnect\n* Cloud NAT\n* Looker (Google Cloud core)\n* Google SecOps SOAR\n* Cloud Firestore\n**Workaround**\n* Customers with service layer retries may see successful completions as only a portion of the zone is affected.\n* Customers that are severely affected and have services available in alternate zones can failover to alternate zones.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Iowa (us-central1)","id":"us-central1"}]},{"created":"2026-09-01T16:19:12+00:00","modified":"2026-09-01T17:09:04+00:00","when":"2026-09-01T16:19:12+00:00","text":"**Summary**\nMultiple products in us-central1-b are experiencing network service degradation.\n**Description**\nThe issue is affecting a portion of the us-central1-b zone. The remaining zones in the region are unaffected.\nFollowing network-level mitigation efforts, the underlying network infrastructure has fully recovered. Product engineering teams across Cloud are currently validating the recovery status of individual services.\nWe will provide more information by Tuesday, 2026-09-01 10:00 US/Pacific with current details.\n**Customer Symptoms**\nCustomers are experiencing elevated packet loss and errors.\n* BigQuery\n* Cloud Dataflow\n* Cloud SQL\n* App Engine\n* Cloud Run\n* AlloyDB\n* Cloud Bigtable\n* Cloud Spanner\n* Compute Engine\n* Cloud VPN\n* Cloud Interconnect\n* Cloud NAT\n* Cloud Filestore\n* Cloud Hybrid Connectivity\n* Virtual Private Cloud\n* Google Kubernetes Engine\n* Looker (Google Cloud core)\n* Apigee\n* Google SecOps SOAR\n**Workaround**\n* Customers with service layer retries may see successful completions as only a portion of the zone is affected.\n* Customers that are severely affected and have services available in alternate zones can failover to alternate zones.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Iowa (us-central1)","id":"us-central1"}]},{"created":"2026-09-01T16:03:12+00:00","modified":"2026-09-01T16:19:12+00:00","when":"2026-09-01T16:03:12+00:00","text":"**Summary**\nMultiple products in us-central1-b are experiencing network service degradation. \n**Description**\nWe are experiencing a networking issue starting Tuesday, 2026-09-01 07:41 US/Pacific.\nThe issue is affecting a portion of the us-central1-b zone. The remaining zones in the region are unaffected.\nOur network engineering team has put in mitigations and we are seeing services starting to recover.\nWe will provide more information by Tuesday, 2026-09-01 09:30 US/Pacific with current details.\nWe apologize to all who are affected by the disruption.\n**Customer Symptoms**\nCustomers are experiencing elevated packet loss and errors.\n* BigQuery\n* Cloud Dataflow\n* Cloud SQL\n* App Engine\n* Cloud Run\n* AlloyDB\n* Cloud Bigtable\n* Cloud Spanner\n* Compute Engine\n* Cloud VPN\n* Cloud Interconnect\n* Cloud NAT\n* Cloud Filestore\n* Cloud Hybrid Connectivity\n* Virtual Private Cloud\n* Google Kubernetes Engine\n* Looker (Google Cloud core)\n**Workaround**\n* Customers with service layer retries may see successful completions as only a portion of the zone is affected.\n* Customers that are severely affected and have services available in alternate zones can failover to alternate zones.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Iowa (us-central1)","id":"us-central1"}]}],"most_recent_update":{"created":"2026-09-29T16:09:46+00:00","modified":"2026-10-17T21:49:14+00:00","when":"2026-09-29T16:09:46+00:00","text":"## Addendum to Incident Report\nThis addendum extends the Detailed Description of Impact from the previous message. Though only two clusters in a datacenter in us-central1-b and us-central1-f experienced network isolation, a few regional products with a dependency on the affected datacenter were also affected. Between 07:41 and 11:52 US/Pacific on Tuesday, September 1, 2026, the following products were affected:\n- **Compute Engine VMs**: VMs running in the affected data center lost network connectivity to resources located outside of their datacenter. From a Compute Engine perspective, this incident only affected a subset of VMs in us-central1-b and us-central1-f.\n- **Zonal and Regional Products Based on Compute Engine** Products with dependencies on VMs in the affected datacenter experienced symptoms like connection timeouts or service unavailability because the underlying VMs lost network connectivity.\nExamples of products that are based on Compute Engine VMs include: Apigee, Cloud SQL, AlloyDB for PostgreSQL, Dataflow, Cloud Filestore, and Looker.\n- **Google Kubernetes Engine (GKE)**: GKE clusters whose control plane had dependencies on Compute Engine VMs in the affected clusters experienced errors and timeouts when administrators or nodes attempted to connect to the Kubernetes API server. Consequently, deployments might have been delayed, Kubernetes API operations might have failed, and new nodes might not have registered with the control plane (causing node pool operational delays).\n- **Cloud Run and App Engine:** Workloads in the us-central1 region experienced elevated serving latency, 5xx aborted request errors, and outbound connectivity degradation. To prevent severe request failures, traffic was diverted to other clusters. Diverting requests to other clusters temporarily caused elevated latency or errors in those clusters.Once the impacted cluster was restored, workload demand for these new backends created a 'thundering herd' of concurrent instance initializations. This sudden surge bypassed warm caches and overwhelmed internal file-serving tiers, extending symptoms until emergency capacity was provisioned.\n- **Other Google APIs and Services**, in us-central1 or a multi-region that includes us-central1, were affected if they had dependencies on software tasks in the affected clusters and weren't able to use software tasks in an unaffected cluster. Symptoms included connection timeouts or service unavailability. Examples of other Google APIs and services are: Google Cloud Bigtable, BigQuery, Google SecOps SOAR, Cloud Spanner, and Cloud Firestore. For some services, symptoms were limited to temporary latency spikes and service unavailability until workloads shifted to unaffected clusters.\n- **Private Service Connect**: Clients (in any region) experienced connectivity issues involving PSC endpoints with dependencies in us-central1, in specific circumstances: - PSC endpoints for Google APIs were affected in the same way as noted in the Google APIs and services section. - Producer/consumer PSC endpoints were affected if the producer had load balancers or backend VMs in the affected clusters of us-central1.\n- **Hybrid Connectivity**: Some Cloud Router, Cloud VPN, and Cloud Interconnect VLAN attachments in us-central1 were affected in specific circumstances: - Cloud Router BGP software tasks for some Cloud Routers in us-central1 experienced a Cloud Router maintenance event if their BGP software tasks were running in the affected clusters. - Cloud VPN tunnel software tasks running in the affected clusters lost network connectivity. This caused some Cloud VPN tunnels in us-central1 to go down until a replacement tunnel task in a different cluster was assigned. - Resources (in any region) sending packets through Cloud Interconnect VLAN attachments in us-central1 might have experienced intermittent connectivity issues in certain situations where network flows weren’t already programmed.\n- **Envoy-based load balancers and other products**: Load balancers and other products that depended on managed Envoy tasks of a proxy-only subnet in us-central1 experienced increased latency or connectivity issues if enough Envoy tasks were in the affected clusters. The following products were affected: - Regional external application load balancers in us-central1 - Regional internal application load balancers in us-central1 - Cross-region internal application load balancers with proxies in us-central1 - Regional external proxy network load balancers in us-central1 - Regional internal proxy network load balancers in us-central1 - Cross-region internal proxy network load balancers with proxies in us-central1 - Secure Web Proxy in us-central1","status":"AVAILABLE","affected_locations":[]},"status_impact":"SERVICE_DISRUPTION","severity":"medium","service_key":"zall","service_name":"Multiple Products","affected_products":[{"title":"AlloyDB for PostgreSQL","id":"fPovtKbaWN9UTepMm3kJ","current_title":"AlloyDB for PostgreSQL"},{"title":"Apigee","id":"9Y13BNFy4fJydvjdsN3X","current_title":"Apigee"},{"title":"Cloud Filestore","id":"jog4nyYkquiLeSK5s26q","current_title":"Cloud Filestore"},{"title":"Cloud Firestore","id":"CETSkT92V21G6A1x28me","current_title":"Cloud Firestore"},{"title":"Cloud Run","id":"9D7d2iNBQWN24zc1VamE","current_title":"Cloud Run"},{"title":"Cloud Spanner","id":"EcNGGUgBtBLrtm4mWvqC","current_title":"Cloud Spanner"},{"title":"Google App Engine","id":"kchyUtnkMHJWaAva8aYc","current_title":"Google App Engine"},{"title":"Google BigQuery","id":"9CcrhHUcFevXPSVaSxkf","current_title":"Google BigQuery"},{"title":"Google Cloud Bigtable","id":"LfZSuE3xdQU46YMFV5fy","current_title":"Google Cloud Bigtable"},{"title":"Google Cloud Dataflow","id":"T9bFoXPqG8w8g1YbWTKY","current_title":"Google Cloud Dataflow"},{"title":"Google Cloud SQL","id":"hV87iK5DcEXKgWU2kDri","current_title":"Google Cloud SQL"},{"title":"Google Compute Engine","id":"L3ggmi3Jy4xJmgodFA9K","current_title":"Google Compute Engine"},{"title":"Google Kubernetes Engine","id":"LCSbT57h59oR4W98NHuz","current_title":"Google Kubernetes Engine"},{"title":"Hybrid Connectivity","id":"5x6CGnZvSHQZ26KtxpK1","current_title":"Hybrid Connectivity"},{"title":"Looker (Google Cloud core)","id":"QEyA1YSaAS3rJS6O8wHp","current_title":"Looker (Google Cloud core)"},{"title":"Virtual Private Cloud (VPC)","id":"BSGtCUnz6ZmyajsjgTKv","current_title":"Virtual Private Cloud (VPC)"}],"uri":"incidents/J5ia5t9p3g9Q5Wi7r8Ev","currently_affected_locations":[],"previously_affected_locations":[{"title":"Multi-region: nam5","id":"nam5"},{"title":"Iowa (us-central1)","id":"us-central1"}]},{"id":"utF3FMFdQfwBzJcGG6vf","number":"5789456648280872492","begin":"2026-08-20T15:40:00+00:00","created":"2026-08-20T16:44:37+00:00","end":"2026-08-20T19:20:00+00:00","modified":"2026-08-27T21:45:02+00:00","external_desc":"We are investigating an issue where customers may experience timeouts, service degradations, errors, and elevated latencies across multiple products in the us-west1 region.","updates":[{"created":"2026-08-27T21:45:02+00:00","modified":"2026-08-27T21:45:02+00:00","when":"2026-08-27T21:45:02+00:00","text":"# Incident Report\n## Summary\nOn Thursday, 20 August 2026, from 08:00 to 10:22 US/Pacific (15:00 to 17:22 UTC), multiple Google Cloud services in the us-west1 region experienced elevated latency, provisioning failures, increased error rates, and widespread service degradations for a total duration of 2 hours and 22 minutes. The incident impacted a wide range of core services — including Persistent Disk, Google Kubernetes Engine, Google Compute Engine, Cloud Run, Google Cloud Bigtable, Cloud Storage, and Identity and Access Management — across both control plane operations and data plane requests.\nWe sincerely apologize for the disruption this incident caused to your business operations and critical workloads. We recognize the vital role Google Cloud plays in supporting your organization, and we deeply regret the impact on your business operations and critical workloads. Engineering and infrastructure teams are actively implementing measures to address the root causes and strengthen network resiliency to prevent recurrences in the future. Specifically, teams are monitoring recovery progress, refining safety checks for planned optical maintenance, and optimizing regional traffic routing mechanisms to safeguard against unexpected capacity constraints.\n## Root Cause\nThe disruption originated during scheduled fiber optic maintenance, which unexpectedly compromised network capacity between data centers within the us-west1 region. Automated rerouting mechanisms failed to properly redistribute traffic to alternate capacity, resulting in network congestion as volumes exceeded available bandwidth in the affected area.\nThis underlying network degradation subsequently impacted higher-level service components through severe packet loss, request throttling, and increased latency across inter-campus dependencies. Core infrastructure services, including Spanner Paxos consensus and the Unified Metadata Server (UMS), experienced significant latency spikes, which cascaded into timeouts and elevated error rates for downstream dependent products such as Cloud Storage, Cloud IAM, Persistent Disk, and Google Kubernetes Engine. Consequently, both control plane operations and data plane requests failed to execute successfully across multiple Google Cloud services in us-west1 throughout the duration of the incident.\n## Remediation and Prevention\nInternal monitoring systems initially detected widespread service anomalies and alerted Google engineers, who promptly confirmed that multiple core services operating across the us-west1 region were severely impacted. In response to the immediate operational risks, engineering teams promptly executed emergency traffic draining protocols to reroute active service workloads away from the compromised inter-campus network infrastructure and minimize further customer disruption. Once teams restored inter-campus fiber network capacity, engineers systematically reintroduced production traffic back to us-west1 through controlled validation stages, ultimately confirming full service normalization across all impacted platforms.\nLonger term engineering remediations and architectural enhancements are actively being finalized and assigned to owning teams. Key focus areas include reforming scheduled maintenance protocols, establishing stricter safety checks and circuit redundancy requirements prior to routine maintenance, and refining automated regional traffic failover mechanisms to automatically handle sudden capacity degradation without incurring severe network congestion.\n## Detailed Description of Impact\nOn Thursday, August 20, between 08:00 and 10:22 US/Pacific, Google Cloud customers in the us-west1 region encountered elevated latency, provisioning failures, and increased error rates.\n* **Impact / Error Rates:** The reduced capacity caused request throttling, latency spikes, and increased retry volume.\n* **Scope Exclusion:** Services and workloads operating in regions other than us-west1 remained fully operational and unaffected.\n**Affected Services and Features**\nThe following services experienced elevated latencies and/or increased error rates, across their respective data planes and control planes:\n* AlloyDB\n* Apache Kafka\n* Apigee Edge Public Cloud\n* Apigee X\n* Artifact Registry\n* BigQuery \u0026 BigQuery Data Transfer Service\n* Cloud Build\n* Cloud Data Fusion\n* Cloud Dataflow\n* Cloud Filestore\n* Cloud Key Management Service (KMS)\n* Cloud Monitoring\n* Cloud Run\n* Cloud SQL\n* Contact Center AI Platform\n* Dataproc Metastore\n* Google App Engine\n* Google Cloud Bigtable\n* Google Cloud Pub/Sub\n* Google Cloud Storage (GCS)\n* Google Compute Engine (GCE)\n* Google Kubernetes Engine (GKE)\n* Identity and Access Management (IAM)\n* Managed Airflow (Cloud Composer)\n* Managed Service for Apache Spark (Dataproc)\n* Persistent Disk\nThe regional incident in us-west1 followed a structured three-phase recovery dictated by platform dependency layers:\nWhile core platform connectivity and live request serving were restored by 10:22 US/Pacific, certain services took additional time to fully recover due to asynchronous backlog processing and localized control-plane state reconciliation for a very small set of customers.\nFor event-driven and pipeline services, inbound error rates dropped to 0 immediately, but some operations experienced elevated latency while workers processed through backlogs accumulated during the outage, clearing later for Cloud Pub/Sub, Cloud Build \u0026 Deploy, Cloud Dataflow, and Cloud Storage lifecycle deletions.\nConcurrently, while primary read/write traffic was healthy across the region, specific long-running lifecycle workflows required extra time to clear locks and reconcile distributed state machines. Compute Engine VM provisioning in zone us-west1-c and Cloud Filestore control plane instance allocation locks and resource validation checks took longer to normalize across regional storage backends.","status":"AVAILABLE","affected_locations":[]},{"created":"2026-08-25T06:20:02+00:00","modified":"2026-08-27T21:45:02+00:00","when":"2026-08-25T06:20:02+00:00","text":"# Preliminary Incident Report\nWe sincerely apologize for the disruption this incident caused to your business operations. Recognizing your reliance on Google Cloud, we express our sincere regrets for any operational impact experienced. Our engineering teams are actively addressing the underlying root cause to prevent future recurrences.\nPlease note that the information provided herein reflects our current understanding as of the time of publication and remains subject to revision as the investigation progresses. A comprehensive Incident Report detailing preventive measures will be issued upon conclusion of our inquiry.\nIf you have experienced impact outside of what is listed below, please reach out to Google Cloud Support using https://cloud.google.com/support.\n## Date/Time of the Issue (All time US/Pacific)\n* Incident Start: 20 August 2026 08:00\n* Incident End: 20 August 2026 10:22\n* Duration: 2 hours, 22 minutes\n## Summary\nOn Thursday, 20 August 2026, multiple Google Cloud services encountered elevated latency, provisioning failures, increased error rates, and service degradations lasting for a duration of 2 hours and 22 minutes.\n## Preliminary Root Cause\nThe disruption originated during scheduled fiber optic maintenance, which unexpectedly compromised network capacity between data centers within the us-west1 region. Automated rerouting mechanisms failed to properly redistribute traffic to alternate capacity, resulting in network congestion as volumes exceeded available bandwidth in the affected area.\nThis underlying network degradation subsequently impacted higher-level service components through request throttling, increased latency, and cascading retries. Consequently, both control plane operations and data plane requests failed to execute successfully across several dependent Google Cloud services, producing the observed latency and elevated error rates.\n## Remediation\nInternal monitoring alerted Google engineers to the incident, confirming that multiple services across us-west1 were affected. To mitigate the immediate operational impact, engineers initiated traffic draining protocols, re-routing service workloads away from the degraded network infrastructure. Following the restoration of inter-campus network capacity and the resolution of the core issue, engineers systematically restored traffic to the us-west1 region and confirmed service normalization.\nLong-term engineering solutions are currently being finalized and assigned to address the root cause and strengthen system resilience regarding fiber maintenance procedures.\n## Description of Impact\nOn Thursday, August 20, between 08:00 and 10:22 US/Pacific, Google Cloud customers in the us-west1 region encountered elevated latency, provisioning failures, and increased error rates.\n* Proportionate Impact / Error Rates: The precise scope of impact—including the proportion of affected projects and applications—and detailed error metrics will be published in the comprehensive Root Cause Analysis, as the reduced capacity caused request throttling, latency spikes, and increased retry volume.\n* Scope Exclusion: Services and workloads operating in regions other than us-west1 remained fully operational and unaffected.\n**Affected Services and Features**\nThe following services experienced elevated latencies and/or increased error rates, across their respective data planes and control planes:\n* AlloyDB\n* Apache Kafka\n* Apigee Edge Public Cloud\n* Apigee X\n* Artifact Registry\n* BigQuery \u0026 BigQuery Data Transfer Service\n* Cloud Build\n* Cloud Data Fusion\n* Cloud Dataflow\n* Cloud Filestore\n* Cloud Key Management Service (KMS)\n* Cloud Monitoring\n* Cloud Run\n* Cloud SQL\n* Contact Center AI Platform\n* Dataproc Metastore\n* Google App Engine\n* Google Cloud Bigtable\n* Google Cloud Pub/Sub\n* Google Cloud Storage (GCS)\n* Google Compute Engine (GCE)\n* Google Kubernetes Engine (GKE)\n* Identity and Access Management (IAM)\n* Managed Airflow (Cloud Composer)\n*Managed Service for Apache Spark (Dataproc)\nPersistent Disk","status":"AVAILABLE","affected_locations":[]},{"created":"2026-08-20T19:37:40+00:00","modified":"2026-08-25T06:20:02+00:00","when":"2026-08-20T19:37:40+00:00","text":"**Summary**\nThe issue causing timeouts, degradations, errors, and latencies across multiple us-west1 products has been mitigated.\n**Description**\nWe have mitigated the issue impacting multiple products in our us-west1 region as of Thursday, 2026-08-20 10:22 PDT.\nOur engineering teams have restored capacity on a planned optical maintenance that caused unexpected congestion in Dalles, Oregon metro /us-west1 region. Our systems stabilized and services have recovered once capacity was restored. Our teams are continuing to monitor for any residual impact.\nWe will publish an analysis of this incident once we have completed our internal investigation.\nWe thank you for your patience while we worked on resolving the issue.\n**Diagnosis / Customer Symptoms**\nCustomers in us-west1 may have experienced timeouts, service degradations, errors, and elevated latencies across multiple products.\n**Workaround**\nThis issue is now mitigated.","status":"AVAILABLE","affected_locations":[]},{"created":"2026-08-20T19:21:07+00:00","modified":"2026-08-20T19:37:40+00:00","when":"2026-08-20T19:21:07+00:00","text":"**Summary**\nThe issue causing timeouts, degradations, errors, and latencies across multiple us-west1 products has been mitigated and we are working to recover all products.\n**Description**\nMitigation actions have been completed by our engineering teams and we are seeing recovery from multiple products. We are continuing to work to recover the remaining products.\nWe will provide an update by Thursday, 2026-08-20 13:30 PDT with details.\n**Diagnosis / Customer Symptoms**\nCustomers in us-west1 may experience timeouts, service degradations, errors, and elevated latencies across multiple products.\n**Workaround**\nNo workarounds needed at this time.","status":"SERVICE_OUTAGE","affected_locations":[{"title":"Oregon (us-west1)","id":"us-west1"}]},{"created":"2026-08-20T18:53:26+00:00","modified":"2026-08-20T19:21:07+00:00","when":"2026-08-20T18:53:26+00:00","text":"**Summary**\nThe issue causing timeouts, degradations, errors, and latencies across multiple us-west1 products has been mitigated and we are working to recover all products.\n**Description**\nMitigation actions have been completed by our engineering teams and we are seeing recovery from multiple products. We are continuing to work to recover the remaining products.\nWe will provide an update by Thursday, 2026-08-20 12:30 PDT with details.\n**Diagnosis / Customer Symptoms**\nCustomers in us-west1 may experience timeouts, service degradations, errors, and elevated latencies across multiple products.\n**Workaround**\nNo workarounds needed at this time.","status":"SERVICE_OUTAGE","affected_locations":[{"title":"Oregon (us-west1)","id":"us-west1"}]},{"created":"2026-08-20T18:03:07+00:00","modified":"2026-08-20T18:53:26+00:00","when":"2026-08-20T18:03:07+00:00","text":"**Summary**\nThe issue causing timeouts, degradations, errors, and latencies across multiple us-west1 products has been mitigated and we are working to recover all products.\n**Description**\nMitigation actions have been completed by our engineering teams and we are seeing recovery from multiple products. We are continuing to work to recover the remaining products.\nWe will provide an update by Thursday, 2026-08-20 11:45 PDT with details.\n**Diagnosis / Customer Symptoms**\nCustomers in us-west1 may experience timeouts, service degradations, errors, and elevated latencies across multiple products.\n**Workaround**\nNo workarounds needed at this time.","status":"SERVICE_OUTAGE","affected_locations":[{"title":"Global","id":"global"},{"title":"Oregon (us-west1)","id":"us-west1"}]},{"created":"2026-08-20T17:32:15+00:00","modified":"2026-08-20T18:03:07+00:00","when":"2026-08-20T17:32:15+00:00","text":"**Summary**\nWe are investigating an issue where customers may experience timeouts, service degradations, errors, and elevated latencies across multiple products in the us-west1 region.\n**Description**\nMitigation actions are implemented by our engineering teams, recovery trends have been observed across infrastructure layers. Active efforts remain underway to bring impacted cloud services back to full operation.\nWe will provide an update by Thursday, 2026-08-20 11:00 PDT with details.\n**Diagnosis / Customer Symptoms**\nCustomers in us-west1 may experience timeouts, service degradations, errors, and elevated latencies across multiple products.\n**Workaround**\nWe recommend customers to failover to other regions where feasible.","status":"SERVICE_OUTAGE","affected_locations":[{"title":"Global","id":"global"},{"title":"Oregon (us-west1)","id":"us-west1"}]},{"created":"2026-08-20T17:13:59+00:00","modified":"2026-08-20T17:32:15+00:00","when":"2026-08-20T17:13:59+00:00","text":"**Summary**\nWe are investigating an issue where customers may experience timeouts, service degradations, errors, and elevated latencies across multiple products in the us-west1 region.\n**Description**\nMitigation actions are implemented by our engineering teams, recovery trends have been observed across infrastructure layers. Active efforts remain underway to bring impacted cloud services back to full operation.\nWe will provide an update by Thursday, 2026-08-20 10:45 PDT with details.\n**Diagnosis / Customer Symptoms**\nCustomers in us-west1 may experience timeouts, service degradations, errors, and elevated latencies across multiple products.\n**Workaround**\nWe recommend customers to failover to other regions where feasible.","status":"SERVICE_OUTAGE","affected_locations":[{"title":"Global","id":"global"},{"title":"Oregon (us-west1)","id":"us-west1"}]},{"created":"2026-08-20T16:44:37+00:00","modified":"2026-08-20T17:13:59+00:00","when":"2026-08-20T16:44:37+00:00","text":"**Summary**\nWe are investigating an issue where customers may experience timeouts, service degradations, errors, and elevated latencies across multiple products in the us-west1 region.\n**Description**\nWe are experiencing an issue with multiple products, beginning on Thursday, 2026-08-20 08:40 PDT.\nOur engineering team continues to investigate the issue.\nWe will provide an update by Thursday, 2026-08-20 10:30 PDT with details.\nWe apologize to all who are affected by the disruption.\n**Diagnosis / Customer Symptoms**\nCustomers in us-west1 may experience timeouts, service degradations, errors, and elevated latencies across multiple products.\n**Workaround**\nNone at this time.","status":"SERVICE_OUTAGE","affected_locations":[{"title":"Global","id":"global"},{"title":"Oregon (us-west1)","id":"us-west1"}]}],"most_recent_update":{"created":"2026-08-27T21:45:02+00:00","modified":"2026-08-27T21:45:02+00:00","when":"2026-08-27T21:45:02+00:00","text":"# Incident Report\n## Summary\nOn Thursday, 20 August 2026, from 08:00 to 10:22 US/Pacific (15:00 to 17:22 UTC), multiple Google Cloud services in the us-west1 region experienced elevated latency, provisioning failures, increased error rates, and widespread service degradations for a total duration of 2 hours and 22 minutes. The incident impacted a wide range of core services — including Persistent Disk, Google Kubernetes Engine, Google Compute Engine, Cloud Run, Google Cloud Bigtable, Cloud Storage, and Identity and Access Management — across both control plane operations and data plane requests.\nWe sincerely apologize for the disruption this incident caused to your business operations and critical workloads. We recognize the vital role Google Cloud plays in supporting your organization, and we deeply regret the impact on your business operations and critical workloads. Engineering and infrastructure teams are actively implementing measures to address the root causes and strengthen network resiliency to prevent recurrences in the future. Specifically, teams are monitoring recovery progress, refining safety checks for planned optical maintenance, and optimizing regional traffic routing mechanisms to safeguard against unexpected capacity constraints.\n## Root Cause\nThe disruption originated during scheduled fiber optic maintenance, which unexpectedly compromised network capacity between data centers within the us-west1 region. Automated rerouting mechanisms failed to properly redistribute traffic to alternate capacity, resulting in network congestion as volumes exceeded available bandwidth in the affected area.\nThis underlying network degradation subsequently impacted higher-level service components through severe packet loss, request throttling, and increased latency across inter-campus dependencies. Core infrastructure services, including Spanner Paxos consensus and the Unified Metadata Server (UMS), experienced significant latency spikes, which cascaded into timeouts and elevated error rates for downstream dependent products such as Cloud Storage, Cloud IAM, Persistent Disk, and Google Kubernetes Engine. Consequently, both control plane operations and data plane requests failed to execute successfully across multiple Google Cloud services in us-west1 throughout the duration of the incident.\n## Remediation and Prevention\nInternal monitoring systems initially detected widespread service anomalies and alerted Google engineers, who promptly confirmed that multiple core services operating across the us-west1 region were severely impacted. In response to the immediate operational risks, engineering teams promptly executed emergency traffic draining protocols to reroute active service workloads away from the compromised inter-campus network infrastructure and minimize further customer disruption. Once teams restored inter-campus fiber network capacity, engineers systematically reintroduced production traffic back to us-west1 through controlled validation stages, ultimately confirming full service normalization across all impacted platforms.\nLonger term engineering remediations and architectural enhancements are actively being finalized and assigned to owning teams. Key focus areas include reforming scheduled maintenance protocols, establishing stricter safety checks and circuit redundancy requirements prior to routine maintenance, and refining automated regional traffic failover mechanisms to automatically handle sudden capacity degradation without incurring severe network congestion.\n## Detailed Description of Impact\nOn Thursday, August 20, between 08:00 and 10:22 US/Pacific, Google Cloud customers in the us-west1 region encountered elevated latency, provisioning failures, and increased error rates.\n* **Impact / Error Rates:** The reduced capacity caused request throttling, latency spikes, and increased retry volume.\n* **Scope Exclusion:** Services and workloads operating in regions other than us-west1 remained fully operational and unaffected.\n**Affected Services and Features**\nThe following services experienced elevated latencies and/or increased error rates, across their respective data planes and control planes:\n* AlloyDB\n* Apache Kafka\n* Apigee Edge Public Cloud\n* Apigee X\n* Artifact Registry\n* BigQuery \u0026 BigQuery Data Transfer Service\n* Cloud Build\n* Cloud Data Fusion\n* Cloud Dataflow\n* Cloud Filestore\n* Cloud Key Management Service (KMS)\n* Cloud Monitoring\n* Cloud Run\n* Cloud SQL\n* Contact Center AI Platform\n* Dataproc Metastore\n* Google App Engine\n* Google Cloud Bigtable\n* Google Cloud Pub/Sub\n* Google Cloud Storage (GCS)\n* Google Compute Engine (GCE)\n* Google Kubernetes Engine (GKE)\n* Identity and Access Management (IAM)\n* Managed Airflow (Cloud Composer)\n* Managed Service for Apache Spark (Dataproc)\n* Persistent Disk\nThe regional incident in us-west1 followed a structured three-phase recovery dictated by platform dependency layers:\nWhile core platform connectivity and live request serving were restored by 10:22 US/Pacific, certain services took additional time to fully recover due to asynchronous backlog processing and localized control-plane state reconciliation for a very small set of customers.\nFor event-driven and pipeline services, inbound error rates dropped to 0 immediately, but some operations experienced elevated latency while workers processed through backlogs accumulated during the outage, clearing later for Cloud Pub/Sub, Cloud Build \u0026 Deploy, Cloud Dataflow, and Cloud Storage lifecycle deletions.\nConcurrently, while primary read/write traffic was healthy across the region, specific long-running lifecycle workflows required extra time to clear locks and reconcile distributed state machines. Compute Engine VM provisioning in zone us-west1-c and Cloud Filestore control plane instance allocation locks and resource validation checks took longer to normalize across regional storage backends.","status":"AVAILABLE","affected_locations":[]},"status_impact":"SERVICE_OUTAGE","severity":"high","service_key":"zall","service_name":"Multiple Products","affected_products":[{"title":"AlloyDB for PostgreSQL","id":"fPovtKbaWN9UTepMm3kJ","current_title":"AlloyDB for PostgreSQL"},{"title":"Apigee Edge Public Cloud","id":"SumcdgBT6GQBzp1vmdXu","current_title":"Apigee Edge Public Cloud"},{"title":"Apigee X","id":"yWJWs53wK43DqGpQRhPV","current_title":"Apigee X"},{"title":"Artifact Registry","id":"QbBuuiRdsLpMr9WmGwm5","current_title":"Artifact Registry"},{"title":"BigQuery Data Transfer Service","id":"UdjkJSWTHMj2b11ftW6E","current_title":"BigQuery Data Transfer Service"},{"title":"Cloud Build","id":"fw8GzBdZdqy4THau7e1y","current_title":"Cloud Build"},{"title":"Cloud Data Fusion","id":"rLKDHeeaBiXTeutF1air","current_title":"Cloud Data Fusion"},{"title":"Cloud Filestore","id":"jog4nyYkquiLeSK5s26q","current_title":"Cloud Filestore"},{"title":"Cloud Key Management Service","id":"67cSySTL7dwJZo9JWUGU","current_title":"Cloud Key Management Service"},{"title":"Cloud Monitoring","id":"3zaaDb7antc73BM1UAVT","current_title":"Cloud Monitoring"},{"title":"Cloud Run","id":"9D7d2iNBQWN24zc1VamE","current_title":"Cloud Run"},{"title":"Contact Center AI Platform","id":"eSAGSSEKoxh8tTJucdYg","current_title":"Contact Center AI Platform"},{"title":"Dataproc Metastore","id":"PXZh68NPz9auRyo4tVfy","current_title":"Dataproc Metastore"},{"title":"Google App Engine","id":"kchyUtnkMHJWaAva8aYc","current_title":"Google App Engine"},{"title":"Google BigQuery","id":"9CcrhHUcFevXPSVaSxkf","current_title":"Google BigQuery"},{"title":"Google Cloud Bigtable","id":"LfZSuE3xdQU46YMFV5fy","current_title":"Google Cloud Bigtable"},{"title":"Google Cloud Dataflow","id":"T9bFoXPqG8w8g1YbWTKY","current_title":"Google Cloud Dataflow"},{"title":"Google Cloud Dataproc","id":"yjXrEg3Yvy26BauMwr69","current_title":"Google Cloud Dataproc"},{"title":"Google Cloud Pub/Sub","id":"dFjdLh2v6zuES6t9ADCB","current_title":"Google Cloud Pub/Sub"},{"title":"Google Cloud SQL","id":"hV87iK5DcEXKgWU2kDri","current_title":"Google Cloud SQL"},{"title":"Google Cloud Storage","id":"UwaYoXQ5bHYHG6EdiPB8","current_title":"Google Cloud Storage"},{"title":"Google Compute Engine","id":"L3ggmi3Jy4xJmgodFA9K","current_title":"Google Compute Engine"},{"title":"Google Kubernetes Engine","id":"LCSbT57h59oR4W98NHuz","current_title":"Google Kubernetes Engine"},{"title":"Identity and Access Management","id":"adnGEDEt9zWzs8uF1oKA","current_title":"Identity and Access Management"},{"title":"Google Cloud Composer","id":"YxkG5FfcC42cQmvBCk4j","current_title":"Managed Airflow"},{"title":"Managed Service for Apache Kafka","id":"QMZ3IpyG3Ooxotv7JOKV","current_title":"Managed Service for Apache Kafka"},{"title":"Persistent Disk","id":"SzESm2Ux129pjDGKWD68","current_title":"Persistent Disk"}],"uri":"incidents/utF3FMFdQfwBzJcGG6vf","currently_affected_locations":[],"previously_affected_locations":[{"title":"Global","id":"global"},{"title":"Oregon (us-west1)","id":"us-west1"}]},{"id":"3BvH3LVGcupoYqV6F4Nw","number":"11738310674864064645","begin":"2026-07-15T23:57:00+00:00","created":"2026-07-16T03:30:59+00:00","end":"2026-07-16T12:25:00+00:00","modified":"2026-07-25T13:16:55+00:00","external_desc":"Google Cloud VMware Engine (GCVE), Google Cloud NetApp Volumes, and Bare Metal Solutions (BMS) services are experiencing a service outage in europe-west4-a due to a cooling failure.","updates":[{"created":"2026-07-25T13:16:55+00:00","modified":"2026-07-25T13:16:55+00:00","when":"2026-07-25T13:16:55+00:00","text":"## \\# Incident Report\n## \\#\\# Summary\nOn Wednesday, 15 July 2026, Google Cloud VMware Engine (GCVE), Bare Metal Solution (BMS), and Google Cloud NetApp Volumes (GCNV) experienced service interruptions for a total duration of 14 hours, 55 minutes.\nThe root cause for this outage is a 3ms voltage drop in the power feed from the utility provider and subsequent utility breaker protective action. This incident was mitigated by the data center provider rectifying the failed systems followed by the Google engineering team restoring the services.\n## \\#\\# Root Cause\nA regional data center hosting services in europe-west4-a experienced an upstream voltage transient affecting both utility power feeds A and B. During this event, the utility breakers on both A and B feeds tripped and initiated the transfer to the back-up power source DRUPS (Diesel Rotary Uninterruptible Power Supply). The transition of side B to DRUPS system was successful without any power interruption. The DRUPS back-up power system for side A failed to take over the facility load due to electrical component failures.\nThe DRUPS failure to take over load initiated automatic transfer of the affected 3 rows from feed A to redundant power feed B. Rows 1 and 2 transferred to power feed B successfully. Row 3 failed to transfer to power feed B and experienced complete power loss due to an overload protection breaker trip. The root cause of the failed transfer on the affected row was identified as load deployment discrepancy which is under further investigation by Google engineering team. This resulted in loss of both redundant power feeds to the single row.\nDuring the voltage transient event, the server data hall experienced an increased temperature due to a cooling system failure. The chiller controller dropped offline during the voltage transient event, failing to signal the chilled water distribution pumps to restart and ultimately causing the chiller system A to shut down. The redundant source was not available due to known ongoing construction work at the facility. This resulted in the data hall temperatures reaching 44°C and subsequent shutdown of the affected data hall machines. Google engineering teams initiated machine shutdown procedures for the remainder of reachable devices as part of the cooling emergency shutdown process.\nA timeline of events during the incident is provided below.\n### DataCenter Events\n| Timestamp(PST) | Event Description |\n| :---- | :---- |\n| 07-15-2026 16:24 | An electrical fault occurred on the utility grid upstream of the data center, disrupting the electrical distribution. |\n| 07-15-2026 16:24 | DRUPS back-up power system for side A failed to take over the data hall load. |\n| 07-15-2026 16:24 | The chiller controller dropped offline during the voltage transient event causing distribution pumps to stop and unable to restart. |\n| 07-15-2026 16:37 | Rows 1 and 2 transferred to power feed B successfully. Row 3 failed to transfer to power feed B and lost power. |\n| 07-15-2026 18:29 | Data hall temperatures reached 44C and crossed the safe machine operating threshold. |\n| 07-15-2026 19:55 | Machine shutdown procedures implemented. |\n| 07-15-2026 21:05 | Cooling system fully recovered and temperatures in the data hall returned to normal operating range. |\n| 07-15-2026 21:24 | Notification about cooling recovery sent by provider |\n| 07-15-2026 21:46 | Notification about power recovery sent by provider |\n### GCVE Timelines\n| Timestamp(PST) | Event Description |\n| :---- | :---- |\n| 07-15-2026 16:30 | GCVE service power monitoring alert received |\n| 07-15-2026 16:41 | First symptom detected, servers reporting redundancy power feed failure. |\n| 07-15-2026 17:05 | Switch temperature \\\u003e60°C alerts triggered. |\n| 07-15-2026 17:09 | Start of user impact, first prober alert failure for north south traffic for customers. |\n| 07-15-2026 19:00 | Server / Network devices shutdown initiated. |\n| 07-15-2026 19:55 | All reachable server/network devices were shut down. |\n| 07-15-2026 21:24 | Cooling system fully recovered and temperatures in the datahall were returning to normal operating range. |\n| 07-15-2026 21:56 | Network restoration started with reachable hydra devices. |\n| 07-15-2026 22:40 | Onsite technician arrived, to recover the console servers. |\n| 07-15-2026 23:10 | Console server reboot/recovery complete. |\n| 07-16-2026 00:33 | Network recovery for all Placement Groups complete. |\n| 07-16-2026 02:36 | Incident mitigated, after recovering all the customer PCs are fully healthy. |\nThis outage impacted 24 private clouds of 20 distinct customers in europe-west4-a region.\n### Bare Metal Solutions (BMS) Timelines\n| Timestamp(PST) | Event Description |\n| :---- | :---- |\n| 07-15-2026 16:41 | First symptom detected, servers and storage reporting redundancy power feed failure |\n| 07-15-2026 17:52 | Automated monitoring detected rising temperatures |\n| 07-15-2026 18:37 | Four Netapp SAN storage nodes failed and were shut down due to overheating, resulting in storage availability issue |\n| 07-15-2026 18:37 | Customer impact started, first server shutdown detected |\n| 07-15-2026 18:59 | Reserve and buffer servers started to get powered off |\n| 07-15-2026 20:43 | Drop in the temperature has been detected |\n| 07-15-2026 20:52 | Four Netapp SAN storage nodes recovered, mitigating storage availability issue |\n| 07-15-2026 21:05 | The cooling system fully recovered and temperatures in the datahall were returning to normal operating range. |\n| 07-15-2026 23:23 | First customer server reboot started |\n| 07-16-2026 06:32 | Last customer server reboot started |\n| 07-16-2026 08:42 | Incident mitigated. All impacted customer servers were rebooted and confirmed in healthy state. |\nThis outage impacted 9 distinct BMS customers in europe-west4\n### NetApp Timelines\n| Timestamp(PST) | Event Description |\n| :---- | :---- |\n| 07-15-2026 16:32 | Netapp facility remote monitoring alert on high temp and network switches switches failure received |\n| 07-15-2026 17:32 | All 6 clusters failed and were shut down automatically due to high temperature |\n| 07-15-2026 21:05 | Cooling capacity restored |\n| 07-15-2026 22:08 | Cluster recovery process initiated for all 6 clusters. 1st cluster recovered |\n| 07-15-2026 23:55 | All 6 Netapp Clusters and all customers recovered and validated as healthy \u0026 operational |\n## \\#\\# Remediation and Prevention\nGoogle engineers were alerted to the infrastructure power loss on Wednesday, 15 July 2026 at 16:30 US/Pacific and subsequent increase in data hall temperatures at 17:44 US/Pacific via our automated monitoring and telemetry, and immediately began investigating.\nDuring the voltage transient event, the chillers maintained power but shut down because the distribution pumps failed to restart, resulting in no water flow. The pumps were manually switched from auto to hand mode to restore circulation and cooling. The facility team deployed an interim portable UPS to support the chiller controllers and prevent localized controller power loss.\nUpon confirmation of utility power restoration, the facility returned to utility power via automatic switching with the exception of two Remote Power Panels (RPPs), which required manual verification before restoration of power to affected server row. To provide full resiliency the facility team aligned a swing DRUPS unit to restore the redundant configuration on the A feed and is working on repairing the faulty DRUPS.\nTo remediate the power loss at Row 3, once the electrical fault was confirmed to be fully isolated, teams reset the tripped breakers, successfully restoring both redundant power to the impacted server racks.\nGoogle is committed to preventing a repeat of this issue in the future and is completing the following actions:\n* Detailed investigation by the engineering team of the sequence of events that prevented transfer of load to DRUPS system and identified system improvements **\\[ETA Aug 2026\\].**\n* Determine and resolve the cause of overload conditions that caused power loss to Row 3 **\\[ETA Aug 2026\\].**\n* Perform investigation of chiller pump control system redundancy setup to ensure cooling system resiliency **\\[ETA Sep 2026\\].**\n* Implement improvements to facility system monitoring alerts for power events and configure early alert thresholds for cooling excursion detection. **\\[ETA Aug 2026\\].**\n* The GCVE engineering team is working to improve the automated triggering of shutdown during quickly evolving thermal runoff situations **\\[ETA Oct 2026\\]**.\n* The BMS engineering team is working with partner teams to update the incident classification and SLO definitions to improve personnel availability during major datacenter events **\\[ETA Sep 2026\\]**.\n* The GCNV engineering team is collaborate with the data center team to review incident handling SLA and runbooks, identify potential future occurrences and create playbooks to address/mitigate them, establish monthly joint emergency drill, and review if the Netapp cluster recovery process can be expedited **\\[ETA Aug 2026\\].**\n## \\#\\# Detailed Description of Impact\nOn 15 July 2026 from 16:39 to 16 July 2026 07:34 US/Pacific, customers experienced service disruptions across several products in europe-west4-a zone:\n* **Google Cloud VMware Engine**: Customers lost connectivity to their private clouds and workloads as foundational hosts and network switches were powered off for thermal protection.\n* **Bare Metal Solution**: Customers experienced connectivity loss to their database servers and storage appliances as the underlying hardware was powered down.\n* **Google Cloud NetApp Volumes**: Customers in the STANDARD, PREMIUM, and EXTREME service levels were unable to access their storage volumes. Control plane operations, including the creation of new storage pools, volumes, and backups, experienced failures in the affected region.","status":"AVAILABLE","affected_locations":[]},{"created":"2026-07-18T00:22:37+00:00","modified":"2026-07-25T13:16:55+00:00","when":"2026-07-18T00:22:37+00:00","text":"# Preliminary Incident Report\nWe sincerely apologize for the disruption this incident caused to your business. We know how much you rely on Google Cloud, and we regret the impact on your productivity.\nPlease note, this information is based on our best knowledge at the time of posting and is subject to change as our investigation continues. A final Incident Report with preventative actions will be posted once our investigation is complete.\nIf you have experienced impact outside of what is listed below, please reach out to Google Cloud Support using https://cloud.google.com/support.\n## Date/Time of the Issue (All time US/Pacific)\n**Google Cloud VMware Engine Impact:**\n- Start: 15 July 2026 17:09\n- End: 16 July 2026 2:33\n- Duration: 9 Hours, 24 Minutes\n**Google Cloud NetApp Volumes Impact:**\n- Start: 15 July 2026 16:39\n- End: 16 July 2026 01:10\n- Duration: 8 Hours 31 Minutes\n**Bare Metal Solution Impact:**\n- Start: 15 July 2026 18:37\n- End: 16 July 2026 07:34\n- Duration: 12 Hours 57 Minutes\n## Summary\nOn Wednesday, 15 July 2026, Google Cloud VMware Engine, Bare Metal Solution, and Google Cloud NetApp Volumes experienced service interruptions for a total duration of 14 hours, 55 minutes. We are taking immediate steps to ensure this doesn’t happen again.\n## Preliminary Root Cause\nA regional data center hosting services in europe-west4-a experienced a loss of utility power and subsequent cooling capacity.\nThe sequence of events leading to customer impact was as follows:\n- An electrical fault occurred on the utility grid upstream of the data center, disrupting the electrical distribution gear and cooling equipment.\n- The loss of cooling infrastructure resulted in ambient temperatures rising rapidly within the affected data halls.\nHost servers, storage clusters, and network switches were shut down to prevent equipment damages due to the extreme heat.\n- The high temperatures in the data hall resulted in disruption to customer workloads and control plane operations across the affected services.\nGoogle engineers have begun a full root cause analysis and we will provide additional information once it is available.\n## Remediation\nGoogle engineering teams were alerted to the issue via automated temperature and hardware unreachability telemetry starting at 16:39 US/Pacific.\nEngineers collaborated with the third-party facility provider to safely restore primary utility power and cooling systems, returning ambient room temperatures to safe operational levels. With the environment stabilized, field support engineers and remote teams systematically booted and verified the server hosts, storage nodes, and network fabric in a controlled sequence. Automated recovery playbooks were executed to restore underlying network switches and routing infrastructure, allowing storage appliances and compute clusters to be brought back online and verified for health. The underlying infrastructure has been fully recovered, and normal operations have been successfully restored.\n## Description of Impact\nOn 15 July 2026 from 16:39 to 16 July 2026 07:34 US/Pacific, customers experienced service disruptions across several products in europe-west4-a zone:\n- **Google Cloud VMware Engine:** Customers lost connectivity to their private clouds and workloads as foundational hosts and network switches were powered off for thermal protection.\n- **Bare Metal Solution:** Customers experienced connectivity loss to their database servers and storage appliances as the underlying hardware was powered down.\n- **Google Cloud NetApp Volumes:** Customers in the STANDARD, PREMIUM, and EXTREME service levels were unable to access their storage volumes. Control plane operations, including the creation of new storage pools, volumes, and backups, experienced failures in the affected region.","status":"AVAILABLE","affected_locations":[]},{"created":"2026-07-16T12:25:47+00:00","modified":"2026-07-18T00:22:37+00:00","when":"2026-07-16T12:25:47+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE), Google Cloud NetApp Volumes, and Bare Metal Solution (BMS) services experienced a service outage in europe-west4-a due to a cooling failure.\n**Description**\nThe datacenter serving europe-west4-a for GCVE, BMS, and NetApp has experienced a power failure, which subsequently caused a cooling failure. Google proactively turned down workloads in order to protect customer data from any risks posed by running infrastructure in a high temperature environment.\nCooling and power have been restored at the site. The issue with GCVE and Google Cloud NetApp Volumes has been resolved for all affected users as of Thursday, 2026-07-16 02:31 PDT and 01:00 PDT respectively.\nThe issue with BMS is largely resolved and is believed to be affecting a very small number of customers. Our Engineering will continue to recover this residual impact directly with the impacted customers.\nIf you have questions or are still impacted, please open a case with the Support Team and we will work with you until this issue is resolved.\n**GCVE:** Service restoration is complete across all the Private Clouds. Customers have been informed about this restoration and requested to verify that their VMs are fully operational.\n**Google Cloud NetApp Volumes:** Service restoration is complete, and all affected servers are now operational.\n**BMS:** Service restoration is largely complete. We continue working with a very small number of remaining affected customers to achieve full recovery.\nWe thank you for your patience while we continue to fully resolve the issue.\n**Customer Symptoms**\nThe issue is now resolved for GCVE and Google Cloud NetApp Volumes. The issue with BMS is largely resolved and our engineering will continue to recover this residual impact directly with the impacted customers.\n**GCVE:** Customers would have observed a loss of connectivity to their private cloud.\n**Google Cloud NetApp Volumes:** Customers would have lost connectivity to ONTAP clusters, as they were proactively shut down to protect these clusters from any damage. Only Standard, Premium, and Extreme service levels were affected.\n**BMS:** Customers may have lost connectivity to their servers. As a protective measure for hardware integrity and recovery, we had shut down some servers in this zone.\n**Workaround**\nNone at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Netherlands (europe-west4)","id":"europe-west4"}]},{"created":"2026-07-16T11:39:12+00:00","modified":"2026-07-16T12:25:47+00:00","when":"2026-07-16T11:39:12+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE), Google Cloud NetApp Volumes, and Bare Metal Solution (BMS) services experienced a service outage in europe-west4-a due to a cooling failure.\n**Description**\nThe datacenter serving europe-west4-a for GCVE, BMS, and NetApp has experienced a power failure, which subsequently caused a cooling failure. Google proactively turned down workloads in order to protect customer data from any risks posed by running infrastructure in a high temperature environment.\nCooling and power have been restored at the site. The issue with GCVE and Google Cloud NetApp Volumes has been resolved for all affected users. We continue to recover the impact for BMS at the moment.\n**GCVE [Mitigated]:** Service restoration is complete across all the Private Clouds. Customers have been informed about this restoration and requested to verify that their VMs are fully operational.\n**Google Cloud NetApp Volumes [Mitigated]:** Service restoration is complete, and all affected servers are now operational. We continue to monitor these for full service recovery.\n**BMS:** Server restoration is largely complete, with most systems now online and reporting a healthy status. We are actively working through the remaining validation efforts to achieve full recovery.\nFor Google Cloud NetApp Volumes and GCVE, if customers are still experiencing impact from this issue, please contact Support, and we will work with you to resolve any residual impact.\nWe will provide the BMS restoration status update by Thursday, 2026-07-16 05:30 PDT with current details.\n**Customer Symptoms**\nThe issue is now resolved for GCVE and Google Cloud NetApp Volumes. We continue to recover the impact for BMS at the moment.\n**GCVE [Mitigated]:** Customers would have observed a loss of connectivity to their private cloud.\n**Google Cloud NetApp Volumes [Mitigated]:** Customers would have lost connectivity to ONTAP clusters, as they were proactively shut down to protect these clusters from any damage. Only Standard, Premium, and Extreme service levels were affected. Customers should now be able to access their volumes again.\n**BMS:** Customers may have lost connectivity to their servers. As a protective measure for hardware integrity and recovery, we had shut down some servers in this zone. We are continuing to restore servers and monitor their health.\n**Workaround**\nNone at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Netherlands (europe-west4)","id":"europe-west4"}]},{"created":"2026-07-16T10:14:07+00:00","modified":"2026-07-16T11:39:12+00:00","when":"2026-07-16T10:14:07+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE), Google Cloud NetApp Volumes, and Bare Metal Solution (BMS) services experienced a service outage in europe-west4-a due to a cooling failure.\n**Description**\nThe datacenter serving europe-west4-a for GCVE, BMS, and NetApp has experienced a power failure, which subsequently caused a cooling failure. Google proactively turned down workloads in order to protect customer data from any risks posed by running infrastructure in a high temperature environment.\nCooling and power have been restored at the site. The issue with GCVE and Google Cloud NetApp Volumes has been resolved for all affected users. We continue to recover the impact for BMS at the moment.\n**GCVE [Mitigated]:** Service restoration is complete across all the Private Clouds. Customers have been informed about this restoration and requested to verify that their VMs are fully operational.\n**Google Cloud NetApp Volumes [Mitigated]:** Service restoration is complete, and all affected servers are now operational. We continue to monitor these for full service recovery.\n**BMS:** Server restoration is largely complete, with most systems now online and reporting a healthy status. We are actively working through the remaining validation efforts to achieve full recovery.\nFor Google Cloud NetApp Volumes and GCVE, if customers are still experiencing impact from this issue, please contact Support, and we will work with you to resolve any residual impact.\nWe will provide the BMS restoration status update by Thursday, 2026-07-16 04:30 PDT with current details.\n**Customer Symptoms**\nThe issue is now resolved for GCVE and Google Cloud NetApp Volumes. We continue to recover the impact for BMS at the moment.\n**GCVE [Mitigated]:** Customers would have observed a loss of connectivity to their private cloud.\n**Google Cloud NetApp Volumes [Mitigated]:** Customers would have lost connectivity to ONTAP clusters, as they were proactively shut down to protect these clusters from any damage. Only Standard, Premium, and Extreme service levels were affected. Customers should now be able to access their volumes again.\n**BMS:** Customers may have lost connectivity to their servers. As a protective measure for hardware integrity and recovery, we had shut down some servers in this zone. We are continuing to restore servers and monitor their health.\n**Workaround**\nNone at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Netherlands (europe-west4)","id":"europe-west4"}]},{"created":"2026-07-16T09:21:21+00:00","modified":"2026-07-16T10:14:07+00:00","when":"2026-07-16T09:21:21+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE), Google Cloud NetApp Volumes, and Bare Metal Solution (BMS) services experienced a service outage in europe-west4-a due to a cooling failure.\n**Description**\nThe datacenter serving europe-west4-a for GCVE, BMS, and NetApp has experienced a power failure, which subsequently caused a cooling failure. Google proactively turned down workloads in order to protect customer data from any risks posed by running infrastructure in a high temperature environment.\nCooling and power have been restored at the site. The datacenter operator team is now validating site stability.\n**GCVE:** Network fabric has been restored, and Private Cloud restoration remains underway. We are notifying the affected customers as their Private Clouds are restored to allow for VM operational verification.\n**BMS:** Server restoration is largely complete, with most systems now online and reporting a healthy status. We are actively working through the remaining validation efforts to achieve full recovery.\n**Google Cloud NetApp Volumes:** Service restoration is complete, and all affected servers are now operational. We continue to monitor these for full service recovery. If customers are still experiencing impact from this issue, please contact Support, and we will work with you to resolve any residual impact.\nWe will provide an update by Thursday, 2026-07-16 03:30 PDT with current details.\n**Customer Symptoms**\n**GCVE:** Customers would have observed a loss of connectivity to their private cloud. As a protective measure for hardware integrity and recovery, we had shut down all Private Clouds in this zone. We are in the process of bringing all restored Private Clouds online.\n**BMS:** Customers may have lost connectivity to their servers. As a protective measure for hardware integrity and recovery, we had shut down some servers in this zone. We are continuing to restore servers and monitor their health.\n**Google Cloud NetApp Volumes:** Customers would have lost connectivity to ONTAP clusters, as they were proactively shut down to protect these clusters from any damage. Only Standard, Premium, and Extreme service levels were affected. Customers should now be able to access their volumes again.\n**Workaround**\nNone at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Netherlands (europe-west4)","id":"europe-west4"}]},{"created":"2026-07-16T08:32:22+00:00","modified":"2026-07-16T09:21:21+00:00","when":"2026-07-16T08:32:22+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE), Google Cloud NetApp Volumes, and Bare Metal Solution (BMS) services experienced a service outage in europe-west4-a due to a cooling failure.\n**Description**\nThe datacenter serving europe-west4-a for GCVE, BMS, and NetApp has experienced a power failure, which subsequently caused a cooling failure. Google proactively turned down workloads in order to protect customer data from any risks posed by running infrastructure in a high temperature environment.\nCooling and power have been restored at the site. The datacenter operator team is now validating site stability.\n**GCVE:** Network fabric has been restored, and Private Cloud restoration remains underway. We are notifying the affected customers as their Private Clouds are restored to allow for VM operational verification.\n**BMS:** Server restoration is largely complete, with most systems now online and reporting a healthy status. We are actively working through the remaining validation efforts to achieve full recovery.\n**Google Cloud NetApp Volumes:** Service restoration is complete, and all affected servers are now operational. We continue to monitor these for full service recovery. If customers are still experiencing impact from this issue, please contact Support, and we will work with you to resolve any residual impact.\nWe will provide an update by Thursday, 2026-07-16 02:30 PDT with current details.\n**Customer Symptoms**\n**GCVE:** Customers would have observed a loss of connectivity to their private cloud. As a protective measure for hardware integrity and recovery, we had shut down all Private Clouds in this zone. We are in the process of bringing all restored Private Clouds online.\n**BMS:** Customers may have lost connectivity to their servers. As a protective measure for hardware integrity and recovery, we had shut down some servers in this zone. We are continuing to restore servers and monitor their health.\n**Google Cloud NetApp Volumes:** Customers would have lost connectivity to ONTAP clusters, as they were proactively shut down to protect these clusters from any damage. Only Standard, Premium, and Extreme service levels were affected. Customers should now be able to access their volumes again.\n**Workaround**\nThere are no workarounds available for this issue at this time. However, customers with multi-regional deployments are advised to route traffic to an alternate site.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Netherlands (europe-west4)","id":"europe-west4"}]},{"created":"2026-07-16T07:39:01+00:00","modified":"2026-07-16T08:32:22+00:00","when":"2026-07-16T07:39:01+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE), Google Cloud NetApp Volumes, and Bare Metal Solution (BMS) services are experiencing a service outage in europe-west4-a due to a cooling failure.\n**Description**\nThe datacenter serving europe-west4-a for GCVE, BMS, and NetApp has experienced a power failure, which subsequently caused a cooling failure. Google proactively turned down workloads in order to protect customer data from any risks posed by running infrastructure in a high temperature environment.\nCooling and power have been restored at the site. The datacenter operator team is now working to safely restart affected workloads.\n**GCVE:** As a precautionary measure, our engineering teams had shut down private clouds to protect these clouds from any damage. Network fabric has been restored, and Private Cloud restoration remains underway. We will notify affected customers once their Private Clouds are restored to allow for VM operational verification.\n**BMS:** We are continuing to restore servers and monitor their health. Customers may be unable to access these systems until service restoration is complete.\n**Google Cloud NetApp Volumes:** Our engineering team had proactively shut down ONTAP clusters to protect the data stored on them. Recovery is currently in progress. Customers may experience unavailability of Cloud NetApp Volumes until this issue is resolved.\nWe will provide an update by Thursday, 2026-07-16 01:30 PDT with current details.\n**Customer Symptoms**\n**GCVE:** Customers would have already observed a loss of connectivity to their private cloud. As a protective measure for hardware integrity and recovery, we have shut down all private clouds in this zone.\n**BMS:** Customers may have lost connectivity to their servers. As a protective measure for hardware integrity and recovery, we shut down some servers in this zone. We are continuing to restore servers and monitor their health. Customers may be unable to access these systems until service restoration is complete.\n**Google Cloud NetApp Volumes:** Customers would have already lost connectivity to ONTAP clusters, as we proactively shut them down to protect these clusters from any damage. Only Standard, Premium, and Extreme service levels are affected.\n**Workaround**\nThere are no workarounds available for this issue at this time. However, customers with multi-regional deployments are advised to route traffic to an alternate site.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Netherlands (europe-west4)","id":"europe-west4"}]},{"created":"2026-07-16T06:29:45+00:00","modified":"2026-07-16T07:39:01+00:00","when":"2026-07-16T06:29:45+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE), Google Cloud NetApp Volumes, and Bare Metal Solution (BMS) services are experiencing a service outage in europe-west4-a due to a cooling failure.\n**Description**\nThe datacenter serving europe-west4-a for GCVE, BMS, and NetApp has experienced a power failure, which subsequently caused a cooling failure. Google proactively turned down workloads in order to protect customer data from any risks posed by running infrastructure in a high temperature environment.\nCooling and power have been restored at the site. The datacenter operator team is now working to safely restart affected workloads.\n**GCVE:** As a precautionary measure, our engineering teams had shut down private clouds to protect these clouds from any damage. Service restoration is still in progress. We will notify customers as soon as their private cloud has been powered back up and it is safe to restart the VMs.\n**BMS:** We are continuing to restore servers and monitor their health. Customers may be unable to access these systems until service restoration is complete.\n**Google Cloud NetApp Volumes:** Our engineering team had proactively shut down ONTAP clusters to protect the data stored on them. Customers may experience unavailability of Cloud NetApp Volumes until this issue is resolved.\nWe will provide an update by Thursday, 2026-07-16 00:30 PDT with current details.\n**Customer Symptoms**\n**GCVE:** Customers would have already observed a loss of connectivity to their private cloud. As a protective measure for hardware integrity and recovery, we have shut down all private clouds in this zone.\n**BMS:** Customers may have lost connectivity to their servers. As a protective measure for hardware integrity and recovery, we shut down some servers in this zone. We are continuing to restore servers and monitor their health. Customers may be unable to access these systems until service restoration is complete.\n**Google Cloud NetApp Volumes:** Customers would have already lost connectivity to ONTAP clusters, as we proactively shut them down to protect these clusters from any damage. Only Standard, Premium, and Extreme service levels are affected.\n**Workaround**\nThere are no workarounds available for this issue at this time. However, customers with multi-regional deployments are advised to route traffic to an alternate site.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Netherlands (europe-west4)","id":"europe-west4"}]},{"created":"2026-07-16T04:41:44+00:00","modified":"2026-07-16T06:31:30+00:00","when":"2026-07-16T04:41:44+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE), Google Cloud NetApp Volumes, and Bare Metal Solution (BMS) services are experiencing a service outage in europe-west4-a due to a cooling failure\n**Description**\nThe datacenter serving europe-west4-a for GCVE, BMS, and NetApp has experienced a power failure, which subsequently caused a cooling failure. Google has proactively turned down workloads in order to protect customer data from any risks posed by running infrastructure in a high temperature environment. The datacenter operator team is working diligently to bring cooling and power back online so we can safely restart affected workloads. Some cooling has been restored, and we are working to restore affected workloads as available capacity allows.\n**GCVE:** Cooling has been restored at the site. As a precautionary measure, our engineering teams had shut down private clouds to protect these clouds from any damage. We are beginning service restoration and will notify customers as soon as their private cloud has been powered back up and it is safe to restart the VMs.\n**BMS:** Some Bare Metal Solution servers experienced high temperatures and we proactively shut them down. We are starting to bring the servers back online, and will provide an update once they are ready. Customers may be unable to access these systems until service is restored.\n**Google Cloud NetApp Volumes:** Our engineering team has proactively shut down ONTAP clusters to protect the data stored on them. Customers may experience unavailability of Cloud NetApp Volumes until this issue is resolved.\nThere is no estimated time for resolution. We will provide an update by Wednesday, 2026-07-15 23:30 PDT with current details.\nWe apologize to all who are affected by the disruption.\n**Customer Symptoms**\n**GCVE:** Customers would have already observed a loss of connectivity to their private cloud. As a protective measure for hardware integrity and recovery, we have shut down all private clouds in this zone.\n**BMS:** Customers may have lost connectivity to their BMS machines. As a protective measure for hardware integrity and recovery, we shut down some servers in this zone, and are actively restoring them. Customers may be unable to access these systems until restoration is complete.\n**Google Cloud NetApp Volumes:** Customers would have already lost connectivity to ONTAP clusters, as we proactively shut them down to protect these clusters from any damage. Only Standard, Premium, and Extreme service levels are affected.\n**Workaround**\nThere are no workarounds available for this issue at this time. However, customers with multi-regional deployments are advised to route traffic to an alternate site.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Netherlands (europe-west4)","id":"europe-west4"}]},{"created":"2026-07-16T04:17:44+00:00","modified":"2026-07-16T06:31:21+00:00","when":"2026-07-16T04:17:44+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE), Google Cloud NetApp Volumes, and Bare Metal Solution (BMS) services are experiencing temperature alerts in europe-west4-a\n**Description**\nThe datacenter serving europe-west4-a for GCVE, BMS, and NetApp has experienced a power failure, which subsequently caused a cooling failure. Google has proactively turned down workloads in order to protect customer data from any risks posed by running infrastructure in a high temperature environment. The datacenter operator team is working diligently to bring cooling and power back online so we can safely restart affected workloads.\n**GCVE:** Our engineering teams have shut down private clouds, and we expect that others will shut down as well. We will notify customers as soon as their private cloud has been powered back up and it is safe to restart the VMs.\n**BMS:** Some Bare Metal Solution servers are experiencing high temperatures and we are in the process of shutting them down. Customers may be unable to access their systems until we resolve the issue.\n**Google Cloud NetApp Volumes** Our engineering team has proactively shut down ONTAP clusters to protect the data stored on them. Customers may experience unavailability of Cloud NetApp Volumes until this issue is resolved. There is no estimated time for resolution. We will provide an update by Wednesday, 2026-07-15 22:30 PDT with current details. We apologize to all who are affected by the disruption.\n**Customer Symptoms**\n**GCVE:** Customers would have already observed a loss of connectivity to their private cloud. As a protective measure for hardware integrity and a recovery, we have shut down all private clouds in this zone.\n**BMS:** Customers may have already lost connectivity to their BMS machines. As a protective measure for hardware integrity and a recovery, we are shutting down some servers in this zone.\n**Google Cloud NetApp Volumes** Customers would have already lost connectivity to ONTAP clusters, as we proactively shut them down for their protection. Only Standard, Premium, and Extreme service levels are affected.\n**Workaround**\nThere are no workarounds available for this issue at this time. Customers with multi-regional deployments are advised to route traffic to an alternate site.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Netherlands (europe-west4)","id":"europe-west4"}]},{"created":"2026-07-16T03:30:59+00:00","modified":"2026-07-16T06:30:59+00:00","when":"2026-07-16T03:30:59+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE), Google Cloud NetApp Volumes, and Bare Metal Solution (BMS) services are experiencing temperature alerts in europe-west4-a.\n**Description**\n**GCVE:** Our engineering teams are currently working with data center facility teams to address the rising temperatures. A shutdown has already occurred for some private clouds, and we expect that others will shut down as well. **We recommend shutting down your VMware workload VMs for precaution so that recovery is safer. A shutdown of all systems started at 19:00 PDT \\[4:00 Local Time (GMT+2)\\]** We will notify you as soon as your Private Cloud has been powered back up and it is safe to restart the VMs.\n**BMS:** Some Bare Metal Solution servers are experiencing high temperatures and we are in the process of shutting them down. Customers may be unable to access their systems until we resolve the issue.\n**Google Cloud NetApp Volumes** Our engineering team has proactively shut down ONTAP clusters to protect the data stored on them. Customers may experience unavailability of Cloud NetApp Volumes until this issue is resolved. There is no estimated time for resolution. We will provide an update by Wednesday, 2026-07-15 21:30 PDT with current details. We apologize to all who are affected by the disruption.\n**Customer Symptoms**\n**GCVE:** Customers may have already observed a loss of connectivity to their private cloud. As a protective measure for hardware integrity and a recovery, we are shutting down all Private Clouds in this zone.\n**BMS:** Customers may have already lost connectivity to their BMS machines. As a protective measure for hardware integrity and a recovery, we are shutting down servers in this zone.\n**Google Cloud NetApp Volumes** Customers may have already lost connectivity to ONTAP clusters, or will lose connectivity to them shortly, as we proactively shut them down for their protection. Only Standard, Premium, and Extreme service levels are affected.\n**Workaround**\nThere are no workarounds available for this issue at this time. Customers with multi-regional deployments are advised to route traffic to an alternate site.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Netherlands (europe-west4)","id":"europe-west4"}]}],"most_recent_update":{"created":"2026-07-25T13:16:55+00:00","modified":"2026-07-25T13:16:55+00:00","when":"2026-07-25T13:16:55+00:00","text":"## \\# Incident Report\n## \\#\\# Summary\nOn Wednesday, 15 July 2026, Google Cloud VMware Engine (GCVE), Bare Metal Solution (BMS), and Google Cloud NetApp Volumes (GCNV) experienced service interruptions for a total duration of 14 hours, 55 minutes.\nThe root cause for this outage is a 3ms voltage drop in the power feed from the utility provider and subsequent utility breaker protective action. This incident was mitigated by the data center provider rectifying the failed systems followed by the Google engineering team restoring the services.\n## \\#\\# Root Cause\nA regional data center hosting services in europe-west4-a experienced an upstream voltage transient affecting both utility power feeds A and B. During this event, the utility breakers on both A and B feeds tripped and initiated the transfer to the back-up power source DRUPS (Diesel Rotary Uninterruptible Power Supply). The transition of side B to DRUPS system was successful without any power interruption. The DRUPS back-up power system for side A failed to take over the facility load due to electrical component failures.\nThe DRUPS failure to take over load initiated automatic transfer of the affected 3 rows from feed A to redundant power feed B. Rows 1 and 2 transferred to power feed B successfully. Row 3 failed to transfer to power feed B and experienced complete power loss due to an overload protection breaker trip. The root cause of the failed transfer on the affected row was identified as load deployment discrepancy which is under further investigation by Google engineering team. This resulted in loss of both redundant power feeds to the single row.\nDuring the voltage transient event, the server data hall experienced an increased temperature due to a cooling system failure. The chiller controller dropped offline during the voltage transient event, failing to signal the chilled water distribution pumps to restart and ultimately causing the chiller system A to shut down. The redundant source was not available due to known ongoing construction work at the facility. This resulted in the data hall temperatures reaching 44°C and subsequent shutdown of the affected data hall machines. Google engineering teams initiated machine shutdown procedures for the remainder of reachable devices as part of the cooling emergency shutdown process.\nA timeline of events during the incident is provided below.\n### DataCenter Events\n| Timestamp(PST) | Event Description |\n| :---- | :---- |\n| 07-15-2026 16:24 | An electrical fault occurred on the utility grid upstream of the data center, disrupting the electrical distribution. |\n| 07-15-2026 16:24 | DRUPS back-up power system for side A failed to take over the data hall load. |\n| 07-15-2026 16:24 | The chiller controller dropped offline during the voltage transient event causing distribution pumps to stop and unable to restart. |\n| 07-15-2026 16:37 | Rows 1 and 2 transferred to power feed B successfully. Row 3 failed to transfer to power feed B and lost power. |\n| 07-15-2026 18:29 | Data hall temperatures reached 44C and crossed the safe machine operating threshold. |\n| 07-15-2026 19:55 | Machine shutdown procedures implemented. |\n| 07-15-2026 21:05 | Cooling system fully recovered and temperatures in the data hall returned to normal operating range. |\n| 07-15-2026 21:24 | Notification about cooling recovery sent by provider |\n| 07-15-2026 21:46 | Notification about power recovery sent by provider |\n### GCVE Timelines\n| Timestamp(PST) | Event Description |\n| :---- | :---- |\n| 07-15-2026 16:30 | GCVE service power monitoring alert received |\n| 07-15-2026 16:41 | First symptom detected, servers reporting redundancy power feed failure. |\n| 07-15-2026 17:05 | Switch temperature \\\u003e60°C alerts triggered. |\n| 07-15-2026 17:09 | Start of user impact, first prober alert failure for north south traffic for customers. |\n| 07-15-2026 19:00 | Server / Network devices shutdown initiated. |\n| 07-15-2026 19:55 | All reachable server/network devices were shut down. |\n| 07-15-2026 21:24 | Cooling system fully recovered and temperatures in the datahall were returning to normal operating range. |\n| 07-15-2026 21:56 | Network restoration started with reachable hydra devices. |\n| 07-15-2026 22:40 | Onsite technician arrived, to recover the console servers. |\n| 07-15-2026 23:10 | Console server reboot/recovery complete. |\n| 07-16-2026 00:33 | Network recovery for all Placement Groups complete. |\n| 07-16-2026 02:36 | Incident mitigated, after recovering all the customer PCs are fully healthy. |\nThis outage impacted 24 private clouds of 20 distinct customers in europe-west4-a region.\n### Bare Metal Solutions (BMS) Timelines\n| Timestamp(PST) | Event Description |\n| :---- | :---- |\n| 07-15-2026 16:41 | First symptom detected, servers and storage reporting redundancy power feed failure |\n| 07-15-2026 17:52 | Automated monitoring detected rising temperatures |\n| 07-15-2026 18:37 | Four Netapp SAN storage nodes failed and were shut down due to overheating, resulting in storage availability issue |\n| 07-15-2026 18:37 | Customer impact started, first server shutdown detected |\n| 07-15-2026 18:59 | Reserve and buffer servers started to get powered off |\n| 07-15-2026 20:43 | Drop in the temperature has been detected |\n| 07-15-2026 20:52 | Four Netapp SAN storage nodes recovered, mitigating storage availability issue |\n| 07-15-2026 21:05 | The cooling system fully recovered and temperatures in the datahall were returning to normal operating range. |\n| 07-15-2026 23:23 | First customer server reboot started |\n| 07-16-2026 06:32 | Last customer server reboot started |\n| 07-16-2026 08:42 | Incident mitigated. All impacted customer servers were rebooted and confirmed in healthy state. |\nThis outage impacted 9 distinct BMS customers in europe-west4\n### NetApp Timelines\n| Timestamp(PST) | Event Description |\n| :---- | :---- |\n| 07-15-2026 16:32 | Netapp facility remote monitoring alert on high temp and network switches switches failure received |\n| 07-15-2026 17:32 | All 6 clusters failed and were shut down automatically due to high temperature |\n| 07-15-2026 21:05 | Cooling capacity restored |\n| 07-15-2026 22:08 | Cluster recovery process initiated for all 6 clusters. 1st cluster recovered |\n| 07-15-2026 23:55 | All 6 Netapp Clusters and all customers recovered and validated as healthy \u0026 operational |\n## \\#\\# Remediation and Prevention\nGoogle engineers were alerted to the infrastructure power loss on Wednesday, 15 July 2026 at 16:30 US/Pacific and subsequent increase in data hall temperatures at 17:44 US/Pacific via our automated monitoring and telemetry, and immediately began investigating.\nDuring the voltage transient event, the chillers maintained power but shut down because the distribution pumps failed to restart, resulting in no water flow. The pumps were manually switched from auto to hand mode to restore circulation and cooling. The facility team deployed an interim portable UPS to support the chiller controllers and prevent localized controller power loss.\nUpon confirmation of utility power restoration, the facility returned to utility power via automatic switching with the exception of two Remote Power Panels (RPPs), which required manual verification before restoration of power to affected server row. To provide full resiliency the facility team aligned a swing DRUPS unit to restore the redundant configuration on the A feed and is working on repairing the faulty DRUPS.\nTo remediate the power loss at Row 3, once the electrical fault was confirmed to be fully isolated, teams reset the tripped breakers, successfully restoring both redundant power to the impacted server racks.\nGoogle is committed to preventing a repeat of this issue in the future and is completing the following actions:\n* Detailed investigation by the engineering team of the sequence of events that prevented transfer of load to DRUPS system and identified system improvements **\\[ETA Aug 2026\\].**\n* Determine and resolve the cause of overload conditions that caused power loss to Row 3 **\\[ETA Aug 2026\\].**\n* Perform investigation of chiller pump control system redundancy setup to ensure cooling system resiliency **\\[ETA Sep 2026\\].**\n* Implement improvements to facility system monitoring alerts for power events and configure early alert thresholds for cooling excursion detection. **\\[ETA Aug 2026\\].**\n* The GCVE engineering team is working to improve the automated triggering of shutdown during quickly evolving thermal runoff situations **\\[ETA Oct 2026\\]**.\n* The BMS engineering team is working with partner teams to update the incident classification and SLO definitions to improve personnel availability during major datacenter events **\\[ETA Sep 2026\\]**.\n* The GCNV engineering team is collaborate with the data center team to review incident handling SLA and runbooks, identify potential future occurrences and create playbooks to address/mitigate them, establish monthly joint emergency drill, and review if the Netapp cluster recovery process can be expedited **\\[ETA Aug 2026\\].**\n## \\#\\# Detailed Description of Impact\nOn 15 July 2026 from 16:39 to 16 July 2026 07:34 US/Pacific, customers experienced service disruptions across several products in europe-west4-a zone:\n* **Google Cloud VMware Engine**: Customers lost connectivity to their private clouds and workloads as foundational hosts and network switches were powered off for thermal protection.\n* **Bare Metal Solution**: Customers experienced connectivity loss to their database servers and storage appliances as the underlying hardware was powered down.\n* **Google Cloud NetApp Volumes**: Customers in the STANDARD, PREMIUM, and EXTREME service levels were unable to access their storage volumes. Control plane operations, including the creation of new storage pools, volumes, and backups, experienced failures in the affected region.","status":"AVAILABLE","affected_locations":[]},"status_impact":"SERVICE_DISRUPTION","severity":"medium","service_key":"zall","service_name":"Multiple Products","affected_products":[{"title":"Bare Metal Solution","id":"5gQF7Qk9XfQ32pStX6Hb","current_title":"Bare Metal Solution"},{"title":"Google Cloud NetApp Volumes","id":"vtzMUyQ4z9CbA1x6z85s","current_title":"Google Cloud NetApp Volumes"},{"title":"VMWare engine","id":"9H6gWUHvb2ZubeoxzQ1Y","current_title":"VMWare engine"}],"uri":"incidents/3BvH3LVGcupoYqV6F4Nw","currently_affected_locations":[],"previously_affected_locations":[{"title":"Netherlands (europe-west4)","id":"europe-west4"}]},{"id":"T8gmtofFSTGT5tbhyciF","number":"5362718329524538692","begin":"2026-07-14T17:00:00+00:00","created":"2026-07-14T20:24:18+00:00","end":"2026-07-15T03:40:00+00:00","modified":"2026-07-24T07:14:47+00:00","external_desc":"Google Cloud VMware Engine (GCVE) Stretched Cluster customers are experiencing zonal outages impacting network connectivity across multiple regions.","updates":[{"created":"2026-07-24T07:10:18+00:00","modified":"2026-07-24T07:14:47+00:00","when":"2026-07-24T07:10:18+00:00","text":"## Incident Report\n## Summary\nOn Tuesday, 14 July 2026 10:00 PT, Google Cloud VMware Engine (GCVE) Stretched Cluster customers in the australia-southeast2 and europe-west3 zones experienced inter-site communication failures.\nThe disruption was traced to a network configuration update that introduced a conflict, causing inter-site communication failures, which triggered VMware Stretched Cluster failover events. Google engineers successfully mitigated the impact by rolling back the issue-causing configuration change and resetting the network state.\nWe sincerely apologize for the disruption this incident caused to your business. We know how much you rely on Google Cloud, and we regret the impact on your productivity. We are working to address the root cause and prevent this from occurring in the future.\n## Root Cause\nA network configuration update intended to prepare the cloud network infrastructure for new capabilities was deployed to the foundational network control plane. While the configuration payload itself was structurally valid, it exposed an implementation gap within the control plane's routing logic.\nThis logical gap caused the underlying network hosts to misconfigure program routing tables. As a result, traffic destined for the private IP address space used by GCVE Stretched Clusters was dropped. Because Stretched Clusters rely on this private address space to establish routing sessions for inter-zonal connectivity, the traffic drops severed communications between the active zones of the clusters, triggering VMware High Availability (HA) failovers.\nStandard routing health-checking protocols, such as Border Gateway Protocol (BGP) and Bidirectional Forwarding Detection (BFD), remained fully functional because their control plane sessions run on separate, unaffected address spaces. Because the control plane remained healthy, standard failover mechanisms failed to detect that the selective private IP range used for inter-zonal data tunneling was being dropped. Automated safeguards did not block the deployment because the configuration passed initial payload validations. The impact only manifested once the update began routing data traffic through the specific affected IP range.\n## Remediation and Prevention\nTo stabilize the environment, engineers identified the working network paths and deployed configuration changes to reroute traffic and restore connectivity. GCVE Stretched Cluster inter-zonal connectivity was completely restored for all supported locations on Tuesday, 14 July 2026 at 20:40 US/Pacific.\nGoogle is committed preventing a repeat of this issue in the future and is completing the following actions:\n* **Expanded Testing:** We are adding more detailed GCVE network setups to our existing testing environments. This allows us to automatically test future network updates against these configurations before they go live.\n* **Service-Level Data Path Failover:** We are implementing additional service-level data path failover mechanisms that actively probe the specific data-tunneling traffic space. This will ensure a path failover is triggered if the data plane itself is degraded even when the BGP control plane remains functional.\n* **Detailed Alerting**: We are adding faster, more specific alerts for connection issues between zones. This builds on our current platform monitoring to catch minor disruptions early and speed up our response.\n* **Improved Cluster Resilience:** We are fine-tuning the cluster's high-availability and storage settings. This makes virtual machines more resilient to short network drops, preventing them from restarting unnecessarily if the main site is still healthy.\n* **Workload Resilience Alignment (Shared Responsibility):** We are proactively reaching out to customers utilizing non-vSAN replicated virtual machine configurations within Stretched Clusters. Because these workloads are pinned to a single zone without active cross-site replication, they cannot survive inter-site network disruptions. We are ready to assist customers in auditing their storage policies, adjusting Stretched Cluster configurations, and planning the secondary zone capacity required to enable robust high-availability failovers.\n## Detailed Description of Impact\nOn Tuesday, 14 July 2026 from 10:00 to 20:40 US/Pacific, customers utilizing GCVE Stretched Clusters in the affected zones (australia-southeast2, and europe-west3) experienced inter-site communication failures. For some customers, depending on their architecture, this disruption led to a VMWare HA event causing VM restarts/movement across zones as designed, host disconnects, VSAN alarms and intermittent access to VMware Management (vCenter/NSX Manager) components.","status":"AVAILABLE","affected_locations":[]},{"created":"2026-07-20T18:31:26+00:00","modified":"2026-07-24T07:10:18+00:00","when":"2026-07-20T18:31:26+00:00","text":"## Preliminary Incident Report\nWe sincerely apologize for the disruption this incident caused to your business. We know how much you rely on Google Cloud, and we regret the impact on your productivity. We are working to address the root cause and prevent this from occurring in the future.\nPlease note, this information is based on our best knowledge at the time of posting and is subject to change as our investigation continues. A final Incident Report with preventative actions will be posted once our investigation is complete.\nIf you have experienced impact outside of what is listed below, please reach out to Google Cloud Support using [**https://cloud.google.com/support**](https://cloud.google.com/support).\n## Date/Time of the Issue (All time US/Pacific)\nIncident Start: 14 July 2026 10:00\nIncident End: 14 July 2026 20:40\nDuration: 10 hours, 40 minutes\n## Summary\nOn Tuesday, 14 July 2026, Google Cloud VMware Engine (GCVE) Stretched Cluster customers in the australia-southeast2 and europe-west3 zones experienced inter-site communication failures.\nThe disruption was traced to a network configuration update that introduced a conflict, causing inter-site communication failures, which triggered VMware Stretch Cluster failover events. Google engineers successfully mitigated the disruption by rolling back the configuration change.\n## Preliminary Root Cause\nA configuration change deployed within the Google Cloud network affected traffic between the VMware Engine stretched cluster zones. This resulted in a loss of connectivity between zones in the stretched cluster deployment.\nGoogle engineers are doing a full root cause analysis and will provide additional information once it is available.\n## Remediation\nTo stabilize the environment, engineers identified the working network paths and deployed configuration changes to reroute traffic and restore connectivity. GCVE stretch cluster inter-zonal connectivity was completely restored for all supported locations on Tuesday, 14 July 2026 at 20:40 US/Pacific.\n## Description of Impact\nOn Tuesday, 14 July 2026 from 10:00 to 20:40 US/Pacific, customers utilizing GCVE stretch clusters in the affected zones (australia-southeast2, and europe-west3) experienced inter-site communication failures. For some customers, depending on their architecture, this disruption led to VMWare HA event causing VM restarts/movement across zones as designed, Host disconnects, VSAN alarms and Intermittent access to VMware Management (vCenter/NSX Manager) components.\n---","status":"AVAILABLE","affected_locations":[]},{"created":"2026-07-15T05:34:26+00:00","modified":"2026-07-20T18:31:26+00:00","when":"2026-07-15T05:34:26+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE) Stretched Cluster customers may have experienced zonal outages impacting network connectivity across multiple regions.\n**Description**\nWe experienced an inter-site communication issue with Google Cloud VMware Engine (GCVE) Stretched Cluster customers beginning Tuesday, 2026-07-14 at 10:00 PDT. We identified the affected customers, and have worked with them to fully mitigate the issue by Tuesday, 2026-07-14 at 21:46 PDT.\nPreliminary analysis indicates that a network configuration update was the cause of the inter-zone network disruption. Our engineering team mitigated the issue by rolling back the faulty configuration to its last-known good value.\nIf customers are still experiencing impact from this issue, please contact Support, and we will work with you to resolve any residual impact.\nWe thank you for your patience while we worked to resolve this issue.\n**Customer Symptoms**\nSome GCVE customers using Stretched Cluster may have experienced inter-site communication failures to their GCVE environments within the affected zones.\n**Workaround**\nThe issue is now mitigated.","status":"AVAILABLE","affected_locations":[]},{"created":"2026-07-15T03:27:54+00:00","modified":"2026-07-15T05:34:26+00:00","when":"2026-07-15T03:27:54+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE) Stretched Cluster customers are experiencing zonal outages impacting network connectivity across multiple regions.\n**Description**\nWe are experiencing an inter-site communication issue with Google Cloud VMware Engine (GCVE) stretched cluster customers beginning Tuesday, 2026-07-14 at 10:00 PDT. We have identified the customers that are affected by this issue and we are working with them on mitigation.\nA remediation rollout is currently in progress to address the underlying network issue.\n**Failover / VM Migration:** Migrating affected VMs to the healthy, secondary zone of your stretch cluster remains the primary mitigation strategy. Because of the complexities surrounding failover risks and secondary zone health, we highly encourage you to open a ticket with Google Cloud Support if you are severely impacted.\nWe do not currently have an ETA for resolution. We will provide another update by Tuesday, 2026-07-14 22:00 PDT with current details.\n**Customer Symptoms**\nSome GCVE customers using Stretched Cluster may experience inter-site communication failures to their GCVE environments within the affected zones.\n**Workaround**\nWhile we work on restoring full connectivity, we recommend the following to restore access to your workloads:\n* VM Migration (recommended): Where possible, migrate your affected VMs to the healthy and unaffected side of the stretch cluster. We strongly recommend consulting with Google Cloud Support before proceeding.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Sydney (australia-southeast1)","id":"australia-southeast1"},{"title":"Melbourne (australia-southeast2)","id":"australia-southeast2"},{"title":"Frankfurt (europe-west3)","id":"europe-west3"}]},{"created":"2026-07-15T01:55:24+00:00","modified":"2026-07-15T03:27:54+00:00","when":"2026-07-15T01:55:24+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE) Stretched Cluster customers are experiencing zonal outages impacting network connectivity across multiple regions.\n**Description**\nWe are experiencing an inter-site communication issue with Google Cloud VMware Engine (GCVE) stretched cluster customers beginning Tuesday, 2026-07-14 at 10:00 PDT. We have identified the customers that are affected by this issue and we are working with them on mitigation.\nA remediation rollout is currently in progress to address the underlying network issue.\n**Failover / VM Migration:** Migrating affected VMs to the healthy, secondary zone of your stretch cluster remains the primary mitigation strategy. Because of the complexities surrounding failover risks and secondary zone health, we highly encourage you to open a ticket with Google Cloud Support if you are severely impacted.\nWe do not currently have an ETA for resolution. We will provide another update by Tuesday, 2026-07-14 20:30 PDT with current details.\n**Customer Symptoms**\nSome GCVE customers using Stretched Cluster may experience inter-site communication failures to their GCVE environments within the affected zones.\n**Workaround**\nWhile we work on restoring full connectivity, we recommend the following workarounds to restore access to your workloads:\n- VM Migration (recommended): Where possible, migrate your affected VMs to the healthy and unaffected side of the stretch cluster. We strongly recommend consulting with Google Support before proceeding.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Sydney (australia-southeast1)","id":"australia-southeast1"},{"title":"Melbourne (australia-southeast2)","id":"australia-southeast2"},{"title":"Frankfurt (europe-west3)","id":"europe-west3"}]},{"created":"2026-07-15T01:15:28+00:00","modified":"2026-07-15T01:55:24+00:00","when":"2026-07-15T01:15:28+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE) Stretched Cluster customers are experiencing zonal outages impacting network connectivity across multiple regions.\n**Description**\nWe are experiencing an inter-site communication issue with Google Cloud VMware Engine (GCVE) stretched cluster customers beginning Tuesday, 2026-07-14 at 10:00 PDT. We have identified the customers that are affected by this issue and we are working with them on mitigation.\nA remediation rollout is currently in progress to address the underlying network issue.\n**Failover / VM Migration:** Migrating affected VMs to the healthy, secondary zone of your stretch cluster remains the primary mitigation strategy. Because of the complexities surrounding failover risks and secondary zone health, we highly encourage you to open a ticket with Google Cloud Support if you are severely impacted.\nWe do not currently have an ETA for resolution. We will provide another update by Tuesday, 2026-07-14 19:00 PDT with current details.\n**Customer Symptoms**\nSome GCVE customers using Stretched Cluster may experience inter-site communication failures to their GCVE environments within the affected zones.\n**Workaround**\nWhile we work on restoring full connectivity, we recommend the following workarounds to restore access to your workloads:\n- VM Migration (recommended): Where possible, migrate your affected VMs to the healthy and unaffected side of the stretch cluster. We strongly recommend consulting with Google Support before proceeding.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Sydney (australia-southeast1)","id":"australia-southeast1"},{"title":"Melbourne (australia-southeast2)","id":"australia-southeast2"},{"title":"Frankfurt (europe-west3)","id":"europe-west3"}]},{"created":"2026-07-15T00:13:18+00:00","modified":"2026-07-15T01:15:28+00:00","when":"2026-07-15T00:13:18+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE) Stretched Cluster customers are experiencing zonal outages impacting network connectivity across multiple regions.\n**Description**\nWe are experiencing an inter-site communication issue with Google Cloud VMware Engine (GCVE) stretched cluster customers beginning Tuesday, 2026-07-14 at 10:00 PDT. We have identified the customers that are affected by this issue and we are working with them on mitigation.\nA remediation rollout is currently in progress to address the underlying network issue.\n**Failover / VM Migration:** Migrating affected VMs to the healthy, secondary zone of your stretch cluster remains the primary mitigation strategy. Because of the complexities surrounding failover risks and secondary zone health, we highly encourage you to open a ticket with Google Cloud Support if you are severely impacted.\nWe do not currently have an ETA for resolution. We will provide another update by Tuesday, 2026-07-14 18:00 PDT with current details.\n**Customer Symptoms**\nSome GCVE customers using Stretched Cluster may experience inter-site communication failures to their GCVE environments within the affected zones.\nUpon further investigation we identified that the northamerica-northeast2 region was not impacted.\n**Workaround**\nWhile we work on restoring full connectivity, we recommend the following workarounds to restore access to your workloads:\n- VM Migration (recommended): Where possible, migrate your affected VMs to the healthy and unaffected side of the stretch cluster. We strongly recommend consulting with Google Support before proceeding.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Sydney (australia-southeast1)","id":"australia-southeast1"},{"title":"Melbourne (australia-southeast2)","id":"australia-southeast2"},{"title":"Frankfurt (europe-west3)","id":"europe-west3"},{"title":"Toronto (northamerica-northeast2)","id":"northamerica-northeast2"}]},{"created":"2026-07-14T23:05:33+00:00","modified":"2026-07-15T00:13:18+00:00","when":"2026-07-14T23:05:33+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE) Stretched Cluster customers are experiencing zonal outages impacting network connectivity across multiple regions.\n**Description**\nWe are experiencing an inter-site communication issue with Google Cloud VMware Engine (GCVE) stretched cluster customers beginning Tuesday, 2026-07-14 at 10:00 PDT. We have identified the customers that are affected by this issue and we are working with them on mitigation.\nOur investigation has identified a recent configuration update that is the likely cause of the inter-zone network disruption. Teams are working on remediation.\n**Failover / VM Migration:** Migrating affected VMs to the healthy, secondary zone of your stretch cluster remains the primary mitigation strategy. Because of the complexities surrounding failover risks and secondary zone health, we highly encourage you to open a ticket with Google Cloud Support if you are severely impacted.\nWe do not currently have an ETA for resolution. We will provide another update by Tuesday, 2026-07-14 17:00 PDT with current details.\n**Customer Symptoms**\nSome GCVE customers using Stretched Cluster may experience inter-site communication failures to their GCVE environments within the affected zones.\n**Workaround**\nWhile we work on restoring full connectivity, we recommend the following workarounds to restore access to your workloads:\n- VM Migration (recommended): Where possible, migrate your affected VMs to the healthy and unaffected side of the stretch cluster. We strongly recommend consulting with Google Support before proceeding.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Sydney (australia-southeast1)","id":"australia-southeast1"},{"title":"Melbourne (australia-southeast2)","id":"australia-southeast2"},{"title":"Frankfurt (europe-west3)","id":"europe-west3"},{"title":"Toronto (northamerica-northeast2)","id":"northamerica-northeast2"}]},{"created":"2026-07-14T22:16:55+00:00","modified":"2026-07-14T23:05:33+00:00","when":"2026-07-14T22:16:55+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE) Stretched Cluster customers are experiencing zonal outages impacting network connectivity across multiple regions.\n**Description**\nWe are experiencing an inter-site communication issue with Google Cloud VMware Engine (GCVE) stretched cluster customers beginning Tuesday, 2026-07-14 at 10:00 PDT. We have identified the customers that are affected by this issue and we are working with them on mitigation.\nOur investigation has identified underlying inter-zone communication failures and Border Gateway Protocol (BGP) session flapping between cluster zones. Specifically, network connectivity has been lost between the affected zones and the witness appliance. Because the witness appliance is currently unreachable, the cluster zones are unable to safely synchronize state. As a result, VMs on the affected sites are becoming isolated and may be left without writable data.\n**Failover / VM Migration:** Migrating affected VMs to the healthy, secondary zone of your stretch cluster remains the primary mitigation strategy. Because of the complexities surrounding failover risks and secondary zone health, we highly encourage you to open a ticket with Google Cloud Support if you are severely impacted.\nWe do not currently have an ETA for resolution. We will provide another update by Tuesday, 2026-07-14 16:00 PDT with current details.\n**Customer Symptoms**\nSome GCVE customers using Stretched Cluster may experience inter-site communication failures to their GCVE environments within the affected zones.\n**Workaround**\nWhile we work on restoring full connectivity, we recommend the following workarounds to restore access to your workloads:\n- VM Migration (recommended): Where possible, migrate your affected VMs to the healthy and unaffected side of the stretch cluster. We strongly recommend consulting with Google Support before proceeding.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Sydney (australia-southeast1)","id":"australia-southeast1"},{"title":"Melbourne (australia-southeast2)","id":"australia-southeast2"},{"title":"Frankfurt (europe-west3)","id":"europe-west3"},{"title":"Toronto (northamerica-northeast2)","id":"northamerica-northeast2"}]},{"created":"2026-07-14T21:31:52+00:00","modified":"2026-07-14T22:16:55+00:00","when":"2026-07-14T21:31:52+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE) Stretched Cluster customers are experiencing zonal outages impacting network connectivity across multiple regions.\n**Description**\nWe are experiencing an inter-site communication issue with Google Cloud VMware Engine (GCVE) stretched cluster customers beginning Tuesday, 2026-07-14 at 10:00 PDT. We have identified the customers that are affected by this issue and we are working with them on mitigation.\nOur preliminary investigation indicates this is stemming from an underlying network connectivity issue affecting the infrastructure that links the zones within a stretch cluster. This disruption is causing synchronization issues between the affected zones. We believe Storage and Compute services remain unaffected, and VMs are running as expected, though connectivity to them may be degraded.\nWe will provide another update by Tuesday, 2026-07-14 15:00 PDT with current details.\n**Customer Symptoms**\nSome GCVE customers using Stretched Cluster may experience inter-site communication failures to their GCVE environments within the affected zones.\n**Workaround**\nWhile we work on restoring full connectivity, we recommend the following workarounds to restore access to your workloads:\n- VM Migration (recommended): Where possible, migrate your affected VMs to the healthy and unaffected side of the stretch cluster. We strongly recommend consulting with Google Support before proceeding.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Melbourne (australia-southeast2)","id":"australia-southeast2"},{"title":"Frankfurt (europe-west3)","id":"europe-west3"},{"title":"Toronto (northamerica-northeast2)","id":"northamerica-northeast2"}]},{"created":"2026-07-14T20:24:18+00:00","modified":"2026-07-14T21:31:52+00:00","when":"2026-07-14T20:24:18+00:00","text":"**Summary**\nGoogle Cloud VMware Engine (GCVE) Stretched Cluster customers are experiencing zonal outages impacting network connectivity across multiple regions.\n**Description**\nWe are experiencing an issue with Google Cloud VMware Engine (GCVE) beginning Tuesday, 2026-07-14 at 10:00 PDT.\nWe are continuing to investigate and mitigate the issue. We believe this disruption is isolated to network connectivity issues for stretch clusters, while Storage and Compute services appear to be unaffected. GCVE VMs are running as expected but customers may experience connectivity issues to the VMs.\nWe will provide another update by Tuesday, 2026-07-14 14:00 PDT with current details.\n**Customer Symptoms**\nSome GCVE customers may experience inter-site communication failures to their GCVE environments within the affected zones.\n**Workaround**\nNone at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Melbourne (australia-southeast2)","id":"australia-southeast2"},{"title":"Frankfurt (europe-west3)","id":"europe-west3"},{"title":"Toronto (northamerica-northeast2)","id":"northamerica-northeast2"}]}],"most_recent_update":{"created":"2026-07-24T07:10:18+00:00","modified":"2026-07-24T07:14:47+00:00","when":"2026-07-24T07:10:18+00:00","text":"## Incident Report\n## Summary\nOn Tuesday, 14 July 2026 10:00 PT, Google Cloud VMware Engine (GCVE) Stretched Cluster customers in the australia-southeast2 and europe-west3 zones experienced inter-site communication failures.\nThe disruption was traced to a network configuration update that introduced a conflict, causing inter-site communication failures, which triggered VMware Stretched Cluster failover events. Google engineers successfully mitigated the impact by rolling back the issue-causing configuration change and resetting the network state.\nWe sincerely apologize for the disruption this incident caused to your business. We know how much you rely on Google Cloud, and we regret the impact on your productivity. We are working to address the root cause and prevent this from occurring in the future.\n## Root Cause\nA network configuration update intended to prepare the cloud network infrastructure for new capabilities was deployed to the foundational network control plane. While the configuration payload itself was structurally valid, it exposed an implementation gap within the control plane's routing logic.\nThis logical gap caused the underlying network hosts to misconfigure program routing tables. As a result, traffic destined for the private IP address space used by GCVE Stretched Clusters was dropped. Because Stretched Clusters rely on this private address space to establish routing sessions for inter-zonal connectivity, the traffic drops severed communications between the active zones of the clusters, triggering VMware High Availability (HA) failovers.\nStandard routing health-checking protocols, such as Border Gateway Protocol (BGP) and Bidirectional Forwarding Detection (BFD), remained fully functional because their control plane sessions run on separate, unaffected address spaces. Because the control plane remained healthy, standard failover mechanisms failed to detect that the selective private IP range used for inter-zonal data tunneling was being dropped. Automated safeguards did not block the deployment because the configuration passed initial payload validations. The impact only manifested once the update began routing data traffic through the specific affected IP range.\n## Remediation and Prevention\nTo stabilize the environment, engineers identified the working network paths and deployed configuration changes to reroute traffic and restore connectivity. GCVE Stretched Cluster inter-zonal connectivity was completely restored for all supported locations on Tuesday, 14 July 2026 at 20:40 US/Pacific.\nGoogle is committed preventing a repeat of this issue in the future and is completing the following actions:\n* **Expanded Testing:** We are adding more detailed GCVE network setups to our existing testing environments. This allows us to automatically test future network updates against these configurations before they go live.\n* **Service-Level Data Path Failover:** We are implementing additional service-level data path failover mechanisms that actively probe the specific data-tunneling traffic space. This will ensure a path failover is triggered if the data plane itself is degraded even when the BGP control plane remains functional.\n* **Detailed Alerting**: We are adding faster, more specific alerts for connection issues between zones. This builds on our current platform monitoring to catch minor disruptions early and speed up our response.\n* **Improved Cluster Resilience:** We are fine-tuning the cluster's high-availability and storage settings. This makes virtual machines more resilient to short network drops, preventing them from restarting unnecessarily if the main site is still healthy.\n* **Workload Resilience Alignment (Shared Responsibility):** We are proactively reaching out to customers utilizing non-vSAN replicated virtual machine configurations within Stretched Clusters. Because these workloads are pinned to a single zone without active cross-site replication, they cannot survive inter-site network disruptions. We are ready to assist customers in auditing their storage policies, adjusting Stretched Cluster configurations, and planning the secondary zone capacity required to enable robust high-availability failovers.\n## Detailed Description of Impact\nOn Tuesday, 14 July 2026 from 10:00 to 20:40 US/Pacific, customers utilizing GCVE Stretched Clusters in the affected zones (australia-southeast2, and europe-west3) experienced inter-site communication failures. For some customers, depending on their architecture, this disruption led to a VMWare HA event causing VM restarts/movement across zones as designed, host disconnects, VSAN alarms and intermittent access to VMware Management (vCenter/NSX Manager) components.","status":"AVAILABLE","affected_locations":[]},"status_impact":"SERVICE_DISRUPTION","severity":"medium","service_key":"9H6gWUHvb2ZubeoxzQ1Y","service_name":"VMWare engine","affected_products":[{"title":"VMWare engine","id":"9H6gWUHvb2ZubeoxzQ1Y","current_title":"VMWare engine"}],"uri":"incidents/T8gmtofFSTGT5tbhyciF","currently_affected_locations":[],"previously_affected_locations":[{"title":"Melbourne (australia-southeast2)","id":"australia-southeast2"},{"title":"Frankfurt (europe-west3)","id":"europe-west3"}]},{"id":"5fGQt4VbkDnr3Yp8PXPr","number":"1464522124090870782","begin":"2026-06-05T07:00:00+00:00","created":"2026-06-10T01:13:50+00:00","end":"2026-06-26T19:00:00+00:00","modified":"2026-06-29T23:06:10+00:00","external_desc":"Network traffic to Google Cloud originating from Delhi, Chennai, Mumbai and surrounding areas is experiencing intermittent periods of elevated latency and possible packet loss.","updates":[{"created":"2026-06-29T23:06:10+00:00","modified":"2026-06-29T23:06:10+00:00","when":"2026-06-29T23:06:10+00:00","text":"**Summary**\nNetwork traffic to Google Cloud originating from Delhi, Chennai, Mumbai and surrounding areas experienced intermittent periods of elevated latency and possible packet loss.\n**Description**\nTraffic rerouting from the impacted Delhi facility caused a subset of Hybrid Connectivity, Virtual Private Cloud (VPC) and Media CDN customers to experience intermittent latency spikes as demand exceeded regional capacity.\nWe completed the augmentation of out-of-region Internet Edge regional peering capacity in Chennai to provide additional load-balancing and redundancy to large ISPs in India. Service to a large portion of Internet Edge peering capacity has been restored to reduce latency in the local Delhi metropolitan area. We are now recovered and returned to normal service as of Friday, 2026-06-26 PDT.\nFollowing safety clearance, our team restored all lost capacity. We have restored capacity between Delhi-Chennai and Delhi-Mumbai and will continue to closely monitor latency deviations and packet drops.\nWe thank you for your patience during the resolution of this issue.\n**Symptoms**\nThe impacted customers may have experienced slightly elevated latency and non-optimal network routing into Google Cloud.\n**Workaround**\nNone","status":"AVAILABLE","affected_locations":[]},{"created":"2026-06-23T22:52:49+00:00","modified":"2026-06-29T23:06:10+00:00","when":"2026-06-23T22:52:49+00:00","text":"**Summary**\nNetwork traffic to Google Cloud originating from Delhi, Chennai, Mumbai and surrounding areas is experiencing intermittent periods of elevated latency and possible packet loss.\n**Description**\nTraffic rerouting from the impacted Delhi facility has caused a subset of Hybrid Connectivity and Virtual Private Cloud (VPC) customers to experience intermittent latency spikes as demand exceeds regional capacity. Media CDN customers may also notice increased latencies.\nInitial traffic mitigations have yielded positive results for some Cloud customers. We have restored a large portion of Internet Edge peering capacity to reduce latency in the local Delhi metropolitan area. Since the last update, we have completed the augmentation of out-of-region Internet Edge regional peering capacity in Chennai to provide additional load-balancing and redundancy to large ISPs in India.\nFollowing safety clearance, our team has accessed the damaged site and is continuing to restore additional capacity throughout this week. We have optimized capacity across network backbones to increase available headroom and augmented our Delhi user-facing backbone capacity. We will continue to closely monitor latency deviations and packet drops.\nWe will provide our next update by Monday, 2026-06-29 at 17:00 PDT.\n**Symptoms**\nCustomers may experience slightly elevated latency and non-optimal network routing into Google Cloud until the affected facility is fully restored.\n**Workaround**\nThere is no workaround at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Delhi (asia-south2)","id":"asia-south2"},{"title":"Global","id":"global"}]},{"created":"2026-06-22T23:51:23+00:00","modified":"2026-06-23T22:52:49+00:00","when":"2026-06-22T23:51:23+00:00","text":"**Summary**\nNetwork traffic to Google Cloud originating from Delhi, Chennai, Mumbai and surrounding areas is experiencing intermittent periods of elevated latency and possible packet loss.\n**Description**\nTraffic rerouting from the impacted Delhi facility has caused a subset of Hybrid Connectivity and Virtual Private Cloud (VPC) customers to experience intermittent latency spikes as demand exceeds regional capacity. Media CDN customers may also notice increased latencies.\nInitial traffic mitigations have yielded positive results for some Cloud customers. We have restored a large portion of Internet Edge peering capacity to reduce latency in the local Delhi metropolitan area. Since the last update, we have completed the augmentation of out-of-region Internet Edge regional peering capacity in Chennai to provide additional load-balancing and redundancy to large ISPs in India.\nFollowing safety clearance, teams obtained access to the damaged site and will further restore additional incremental user-facing backbone capacity on Tuesday, 2026-06-23. We have optimized capacity across network backbones to increase available headroom, and augmented our Delhi user-facing backbone capacity. We will continue to closely monitor latency deviations and packet drops.\nWe will provide our next update by Tuesday, 2026-06-23 at 17:00 PDT.\n**Symptoms**\nCustomers may experience slightly elevated latency and non-optimal network routing into Google Cloud until the affected facility is fully restored.\n**Workaround**\nThere is no workaround at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Delhi (asia-south2)","id":"asia-south2"},{"title":"Global","id":"global"}]},{"created":"2026-06-17T22:36:07+00:00","modified":"2026-06-22T23:51:23+00:00","when":"2026-06-17T22:36:07+00:00","text":"**Summary**\nNetwork traffic to Google Cloud originating from Delhi, Chennai, Mumbai and surrounding areas is experiencing intermittent periods of elevated latency and possible packet loss.\n**Description**\nTraffic rerouting from the impacted Delhi facility has caused a subset of Hybrid Connectivity and Virtual Private Cloud (VPC) customers to experience intermittent latency spikes as demand exceeds regional capacity. Media CDN customers may also notice increased latencies.\nInitial traffic mitigations have yielded positive results for some Cloud customers. We have restored a portion of Internet Edge peering capacity to reduce latency in the local Delhi metropolitan area. Further, we are nearly finished with the augmentation of out-of-region Internet Edge regional peering capacity in Chennai to provide additional load-balancing and redundancy to large ISPs in India.\nWe have optimized capacity across network backbones to increase available headroom. Additionally, we have augmented our Delhi backbone capacity. We have also restored additional capacity between Delhi-Chennai and Delhi-Mumbai. We will continue to closely monitor latency deviations and packet drops.\nWe will provide our next update by Monday, 2026-06-22 17:00 PDT.\n**Symptoms**\nCustomers may experience slightly elevated latency and non-optimal network routing into Google Cloud until the affected facility is fully restored.\n**Workaround**\nThere is no workaround at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Delhi (asia-south2)","id":"asia-south2"},{"title":"Global","id":"global"}]},{"created":"2026-06-15T23:11:38+00:00","modified":"2026-06-17T22:36:07+00:00","when":"2026-06-15T23:11:38+00:00","text":"**Summary**\nNetwork traffic to Google Cloud originating from Delhi, Chennai, Mumbai and surrounding areas is experiencing intermittent periods of elevated latency and possible packet loss.\n**Description**\nA fire at a third-party data center facility required an emergency power shutdown of networking equipment, isolating a non-compute local Point of Presence (POP) in Delhi and reducing available network capacity in the metro area.\nWe rerouted significant traffic from the impacted facility in Delhi to address reduced local serving capabilities. As a result, a subset of Hybrid Connectivity and Virtual Private Cloud (VPC) customers may be impacted by the routing changes made to address reduced local, latency-optimized serving capabilities in Delhi. Affected customers may experience intermittent latency spikes due to demand exceeding capacity across Indian metros and regional ISPs. Media CDN customers may have experienced higher latencies than normal.\nInitial traffic mitigations have yielded positive results for some Cloud customers. We have restored a portion of Internet Edge peering capacity to reduce latency in the local Delhi metropolitan area. Further, we are augmenting out-of-region Internet Edge regional peering capacity in Chennai to provide additional load-balancing and redundancy to large ISPs in India (expected to be done by Wednesday, 2026-06-17 PDT). We have optimized capacity across network backbones to increase available headroom. Additionally, we have augmented our Delhi backbone capacity over the weekend. We will continue to closely monitor latency deviations and packet drops.\nWe will provide our next update by Wednesday, 2026-06-17 at 17:00 PDT.\n**Symptoms**\nCustomers may experience slightly elevated latency and non-optimal network routing into Google Cloud until the affected facility is fully restored.\n**Workaround**\nThere is no workaround at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Delhi (asia-south2)","id":"asia-south2"},{"title":"Global","id":"global"}]},{"created":"2026-06-12T22:50:20+00:00","modified":"2026-06-15T23:11:38+00:00","when":"2026-06-12T22:50:20+00:00","text":"**Summary**\nNetwork traffic to Google Cloud originating from Delhi, Chennai, Mumbai and surrounding areas is experiencing intermittent periods of elevated latency and possible packet loss.\n**Description**\nA fire at a third-party data center facility required an emergency power shutdown of networking equipment, isolating a non-compute local Point of Presence (POP) in Delhi and reducing available network capacity in the metro area.\nWe rerouted significant traffic from the impacted facility in Delhi to address reduced local serving capabilities. As a result, a subset of Hybrid Connectivity and Virtual Private Cloud (VPC) customers may be impacted by the routing changes made to address reduced local, latency-optimized serving capabilities in Delhi. Affected customers may experience intermittent latency spikes due to demand exceeding capacity across Indian metros and regional ISPs.\nInitial traffic mitigations have yielded positive results for some Cloud customers. In parallel, we are pursuing additional Internet Edge peering capacity to reduce latency in the local Delhi metropolitan area. Further, we are augmenting out-of-region Internet Edge regional peering capacity in Chennai to provide additional load-balancing and redundancy to large ISPs in India (expected to be done by Wednesday, 2026-06-17 PDT). We have optimized capacity across network backbones to increase available headroom. Additionally, we are further augmenting our Delhi backbone capacity (expected to be complete by Monday, 2026-06-15 PDT). We will continue to closely monitor latency deviations and packet drops.\nWe will provide our next update by Monday, 2026-06-15 17:00 PDT.\n**Symptoms**\nCustomers may experience slightly elevated latency and non-optimal network routing into Google Cloud until the affected facility is fully restored.\n**Workaround**\nThere is no workaround at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Delhi (asia-south2)","id":"asia-south2"}]},{"created":"2026-06-11T23:25:15+00:00","modified":"2026-06-12T22:50:20+00:00","when":"2026-06-11T23:25:15+00:00","text":"**Summary**\nNetwork traffic to Google Cloud originating from Delhi, Chennai, Mumbai and surrounding areas is experiencing intermittent periods of elevated latency and possible packet loss.\n**Description**\nA fire at a third-party data center facility required an emergency power shutdown of networking equipment, isolating a non-compute local Point of Presence (POP) in Delhi and reducing available network capacity in the metro area.\nWe rerouted significant traffic from the impacted facility in Delhi to address reduced local serving capabilities. As a result, a subset of Hybrid Connectivity and Virtual Private Cloud (VPC) customers may be impacted by the routing changes made to address reduced local, latency-optimized serving capabilities in Delhi. Affected customers may experience intermittent latency spikes due to demand exceeding capacity across Indian metros and regional ISPs.\nInitial traffic mitigations have yielded positive results for some Cloud customers. In parallel, we are pursuing additional Internet Edge peering capacity to reduce existing fragility in the metro. We are also optimizing capacity across network backbones to increase additional headroom for VPC customers in the affected region. Additionally, we are planning to augment our local Delhi POP and migrating select peering partners to further increase regional capacity. We will continue to closely monitor latency deviations and packet drops.\nWe will provide our next update by Friday, 2026-06-12 at 17:00 PDT.\n**Symptoms**\nCustomers may experience slightly elevated latency and non-optimal network routing into Google Cloud until the affected facility is fully restored.\n**Workaround**\nThere is no workaround at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Delhi (asia-south2)","id":"asia-south2"}]},{"created":"2026-06-10T22:25:38+00:00","modified":"2026-06-11T23:25:15+00:00","when":"2026-06-10T22:25:38+00:00","text":"**Summary**\nNetwork traffic to Google Cloud originating from Delhi, Chennai, Mumbai and surrounding areas is experiencing intermittent periods of elevated latency and possible packet loss.\n**Description**\nA fire at a third-party data center facility required an emergency power shutdown of networking equipment, isolating a non-compute local Point of Presence (POP) in Delhi and reducing available network capacity in the metro area.\nWe rerouted significant traffic from the impacted facility in Delhi to address reduced local serving capabilities. As a result, a subset of Hybrid Connectivity and Virtual Private Cloud (VPC) customers may be impacted by the routing changes made to address reduced local, latency-optimized serving capabilities in Delhi. Affected customers may experience intermittent latency spikes due to demand exceeding capacity across Indian metros and regional ISPs.\nWe are investigating additional traffic mitigations and Internet Edge peering augmentation to alleviate the latency issues affecting our customers. We are continuing to work with the ISP partners in the region to mitigate any additional impact from unplanned failures.\nWe will provide our next update by Thursday, 2026-06-11 17:00 PDT.\n**Symptoms**\nCustomers may experience slightly elevated latency and non-optimal network routing into Google Cloud until the affected facility is fully restored.\n**Workaround**\nThere is no workaround at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Delhi (asia-south2)","id":"asia-south2"}]},{"created":"2026-06-10T01:13:50+00:00","modified":"2026-06-10T22:25:38+00:00","when":"2026-06-10T01:13:50+00:00","text":"**Summary**\nNetwork traffic to Google Cloud originating from Delhi, Chennai, Mumbai and surrounding areas is experiencing intermittent periods of elevated latency and possible packet loss.\n**Description**\nA fire at a third-party data center facility required an emergency power shutdown of networking equipment, isolating a non-compute local Point of Presence (POP) in Delhi and reducing available network capacity in the metro area.\nWe rerouted significant traffic from the impacted facility in Delhi to address reduced local serving capabilities. As a result, a subset of Hybrid Connectivity and Virtual Private Cloud (VPC) customers may be impacted by the routing changes made to address reduced local, latency-optimized serving capabilities in Delhi. Affected customers may experience intermittent latency spikes due to demand exceeding capacity across Indian metros and regional ISPs.\nWe are investigating additional traffic mitigations and Internet Edge peering augmentation to alleviate the latency issues affecting our customers.\nWe will provide our next update by Wednesday, 2026-06-10 17:00 PDT.\n**Symptoms**\nCustomers may experience slightly elevated latency and non-optimal network routing into Google Cloud until the affected facility is fully restored.\n**Workaround**\nThere is no workaround at this time.","status":"SERVICE_DISRUPTION","affected_locations":[{"title":"Delhi (asia-south2)","id":"asia-south2"}]}],"most_recent_update":{"created":"2026-06-29T23:06:10+00:00","modified":"2026-06-29T23:06:10+00:00","when":"2026-06-29T23:06:10+00:00","text":"**Summary**\nNetwork traffic to Google Cloud originating from Delhi, Chennai, Mumbai and surrounding areas experienced intermittent periods of elevated latency and possible packet loss.\n**Description**\nTraffic rerouting from the impacted Delhi facility caused a subset of Hybrid Connectivity, Virtual Private Cloud (VPC) and Media CDN customers to experience intermittent latency spikes as demand exceeded regional capacity.\nWe completed the augmentation of out-of-region Internet Edge regional peering capacity in Chennai to provide additional load-balancing and redundancy to large ISPs in India. Service to a large portion of Internet Edge peering capacity has been restored to reduce latency in the local Delhi metropolitan area. We are now recovered and returned to normal service as of Friday, 2026-06-26 PDT.\nFollowing safety clearance, our team restored all lost capacity. We have restored capacity between Delhi-Chennai and Delhi-Mumbai and will continue to closely monitor latency deviations and packet drops.\nWe thank you for your patience during the resolution of this issue.\n**Symptoms**\nThe impacted customers may have experienced slightly elevated latency and non-optimal network routing into Google Cloud.\n**Workaround**\nNone","status":"AVAILABLE","affected_locations":[]},"status_impact":"SERVICE_DISRUPTION","severity":"medium","service_key":"zall","service_name":"Multiple Products","affected_products":[{"title":"Hybrid Connectivity","id":"5x6CGnZvSHQZ26KtxpK1","current_title":"Hybrid Connectivity"},{"title":"Media CDN","id":"FK8WX6iZ3FuQL6qUwski","current_title":"Media CDN"},{"title":"Virtual Private Cloud (VPC)","id":"BSGtCUnz6ZmyajsjgTKv","current_title":"Virtual Private Cloud (VPC)"}],"uri":"incidents/5fGQt4VbkDnr3Yp8PXPr","currently_affected_locations":[],"previously_affected_locations":[{"title":"Delhi (asia-south2)","id":"asia-south2"},{"title":"Global","id":"global"}]},{"id":"41E5S3mkTGDfkZuJZH5k","number":"6876619551109882402","begin":"2026-02-27T12:37:00+00:00","created":"2026-02-27T16:12:30+00:00","end":"2026-02-27T14:35:00+00:00","modified":"2026-03-09T05:25:43+00:00","external_desc":"Vertex AI Gemini API customers experienced increased error rates when accessing the global endpoint.","updates":[{"created":"2026-03-09T05:25:43+00:00","modified":"2026-03-09T05:25:43+00:00","when":"2026-03-09T05:25:43+00:00","text":"# Incident Report\n## Summary\nOn Friday, 27 February 2026 at 04:37 US/Pacific, customers using Vertex AI Gemini API models experienced increased error rates. Impacted services included Google Cloud Support, Agent Assist, Vertex Gemini API and Dialogflow CX in US regions and the global endpoint. The issue persisted for a duration of 1 hour and 58 minutes.\nThis is not the level of quality and reliability we strive to offer you, and we have taken immediate steps to improve the platform’s performance and availability.\n## Root Cause\nThis incident was caused by a configuration change to a safety filtering service that supports all Gemini models. For some specific requests, this created code paths that eventually led to service disruptions and capacity loss for the safety filtering service. Consequently, customers encountered overload (429 and 503) errors for their queries, with some users reporting elevated error rates for specific models in US regions.\n## Remediation and Prevention\nGoogle engineers were alerted to the issue via our automated monitoring system on Friday, 27 February 2026 04:54 US/Pacific and immediately started an investigation.\nEngineers identified the faulty configuration change and initiated a rollback to restore the previous stable configuration. Engineers also added more capacity to the service to stabilize it. Full service restoration was confirmed by 06:35 US/Pacific as the rollback propagated and servers became healthy. \\ \\\nGoogle is committed to preventing a repeat of this issue and is taking the following actions:\n* Reinforcing rollout processes to include mandatory validation checkpoints.\n* Improving alerting systems to monitor critical dependencies more closely.\n## ## Detailed Description of Impact\nOn Friday, 27 February 2026 between 04:37 and 06:35 US/Pacific, customers accessing Vertex Gemini APIs may have experienced the following:\n* **Affected Models:** All Vertex AI Gemini API models were affected, including gemini-2.5-flash, gemini-2.5-flash-lite, gemini-2.5-pro, gemini-3.0-flash-preview, gemini-3.0-pro-preview, gemini-2.0-flash, gemini-2.0-flash-lite.\n* **Error Experience:** * **PayGo Customers:** Experienced primarily 429 Resource Exhausted errors. * **Provisioned Throughput (PT) Customers:** Received 503 Service Unavailable errors. * For PT customers, most errors stopped at **06:00**. For PayGo customers, most errors stopped at **06:20**.\n* **Geographic Scope:** Global endpoint, us-central1, us-east4, and other US regions were impacted.","status":"AVAILABLE","affected_locations":[]},{"created":"2026-03-04T23:23:18+00:00","modified":"2026-03-09T05:25:43+00:00","when":"2026-03-04T23:23:18+00:00","text":"# Preliminary Incident Report\nWe apologize for the inconvenience this service disruption may have caused. We would like to provide some information about this incident below. Please note, this information is based on our best knowledge at the time of posting and is subject to change as our investigation continues. A final Incident Report with preventative actions will be posted once our investigation is complete. If you have experienced impact outside of what is listed below, please reach out to Google Cloud Support using https://cloud.google.com/support.\n## Date/Time of the Issue (All time US/Pacific)\nIncident Start: 27 February 2026 04:37\nIncident End: 27 February 2026 06:35\nDuration: 1 hour, 58 minutes\n## Summary\nOn Friday, 27 February 2026 at 04:37 US/Pacific, customers using Vertex AI Gemini API models (including Gemini 2.0, 2.5, and 3.0 previews) experienced increased error rates. Impacted services included Google Cloud Support, Agent Assist, the Vertex Gemini API and Dialogflow CX in US regions and the global endpoint for a duration of 1 hour and 58 minutes.\nThis is not the level of quality and reliability we strive to offer you, and we are taking immediate steps to improve the platform’s performance and availability.\n## Preliminary Root Cause\nThis incident was caused by a configuration change to a safety filtering service that supports all Gemini models. This configuration change enabled a code path that interacted poorly with specific requests, leading to service disruption for the safety filtering service. This in turn led to customers seeing overload (429 and 503) errors for their queries.\nGoogle engineers have begun a full root cause analysis and will provide additional information once it is available.\n## Remediation\nGoogle engineers were alerted to the service disruption via automated alert on Friday, 27 February 2026 04:54 US/Pacific and immediately started an investigation.\nEngineers identified the faulty configuration change for a safety filtering service and initiated a rollback to restore the previous stable configuration. Additionally, engineers added more capacity to the service. Full service restoration was confirmed by 06:35 US/Pacific as the rollback propagated and servers became healthy.\n## Description of Impact\nOn Friday, 27 February 2026 between 04:37 and 06:35 US/Pacific, customers accessing Vertex Gemini APIs may have experienced the following:\n- Affected Models: All Gemini versions were affected, including gemini-2.5-flash, gemini-2.5-flash-lite, gemini-2.5-pro, gemini-3.0-flash-preview, gemini-3.0-pro-preview, gemini-2.0-flash, gemini-2.0-flash-lite.\n- Error Experience: - PayGo Customers: Experienced primarily 429 Resource Exhausted errors. - Provisioned Throughput (PT) Customers: Received 503 Service Unavailable errors. - For PT customers, most errors stopped at 06:00. For PayGo customers, most errors stopped at 06:20.\n- Geographic Scope: Global endpoint, us-central1, us-east4, and other US regions were impacted.","status":"AVAILABLE","affected_locations":[]},{"created":"2026-02-27T16:12:30+00:00","modified":"2026-03-04T23:23:18+00:00","when":"2026-02-27T16:12:30+00:00","text":"**Description** \\\nBetween Friday, 2026-02-27, 04:36 and 06:45 PST, customers experienced increased error rates when accessing the Vertex Gemini API Global endpoint. The issue impacted API requests to multiple Gemini models.\nThe incident also caused downstream impact to Dialogflow CX, Agent Assist, Google Cloud Support AI agent, and Customer Experience Agent Studio, which rely on Gemini APIs.\nPreliminary analysis indicates the issue was triggered by a recent configuration change. Service was fully restored after the configuration change was rolled back.\nWe thank you for your patience while we worked on resolving the issue.\n**Symptom**\n\\\nCustomers experienced increased error rates when sending API requests to impacted multiple Gemini models through the global endpoint.","status":"SERVICE_INFORMATION","affected_locations":[{"title":"Montréal (northamerica-northeast1)","id":"northamerica-northeast1"},{"title":"São Paulo (southamerica-east1)","id":"southamerica-east1"},{"title":"Iowa (us-central1)","id":"us-central1"},{"title":"South Carolina (us-east1)","id":"us-east1"},{"title":"Northern Virginia (us-east4)","id":"us-east4"},{"title":"Columbus (us-east5)","id":"us-east5"},{"title":"Oregon (us-west1)","id":"us-west1"}]}],"most_recent_update":{"created":"2026-03-09T05:25:43+00:00","modified":"2026-03-09T05:25:43+00:00","when":"2026-03-09T05:25:43+00:00","text":"# Incident Report\n## Summary\nOn Friday, 27 February 2026 at 04:37 US/Pacific, customers using Vertex AI Gemini API models experienced increased error rates. Impacted services included Google Cloud Support, Agent Assist, Vertex Gemini API and Dialogflow CX in US regions and the global endpoint. The issue persisted for a duration of 1 hour and 58 minutes.\nThis is not the level of quality and reliability we strive to offer you, and we have taken immediate steps to improve the platform’s performance and availability.\n## Root Cause\nThis incident was caused by a configuration change to a safety filtering service that supports all Gemini models. For some specific requests, this created code paths that eventually led to service disruptions and capacity loss for the safety filtering service. Consequently, customers encountered overload (429 and 503) errors for their queries, with some users reporting elevated error rates for specific models in US regions.\n## Remediation and Prevention\nGoogle engineers were alerted to the issue via our automated monitoring system on Friday, 27 February 2026 04:54 US/Pacific and immediately started an investigation.\nEngineers identified the faulty configuration change and initiated a rollback to restore the previous stable configuration. Engineers also added more capacity to the service to stabilize it. Full service restoration was confirmed by 06:35 US/Pacific as the rollback propagated and servers became healthy. \\ \\\nGoogle is committed to preventing a repeat of this issue and is taking the following actions:\n* Reinforcing rollout processes to include mandatory validation checkpoints.\n* Improving alerting systems to monitor critical dependencies more closely.\n## ## Detailed Description of Impact\nOn Friday, 27 February 2026 between 04:37 and 06:35 US/Pacific, customers accessing Vertex Gemini APIs may have experienced the following:\n* **Affected Models:** All Vertex AI Gemini API models were affected, including gemini-2.5-flash, gemini-2.5-flash-lite, gemini-2.5-pro, gemini-3.0-flash-preview, gemini-3.0-pro-preview, gemini-2.0-flash, gemini-2.0-flash-lite.\n* **Error Experience:** * **PayGo Customers:** Experienced primarily 429 Resource Exhausted errors. * **Provisioned Throughput (PT) Customers:** Received 503 Service Unavailable errors. * For PT customers, most errors stopped at **06:00**. For PayGo customers, most errors stopped at **06:20**.\n* **Geographic Scope:** Global endpoint, us-central1, us-east4, and other US regions were impacted.","status":"AVAILABLE","affected_locations":[]},"status_impact":"SERVICE_INFORMATION","severity":"low","service_key":"zall","service_name":"Multiple Products","affected_products":[{"title":"Agent Assist","id":"eUntUKqUrHdbBLNcVVXq","current_title":"Agent Assist"},{"title":"Dialogflow CX","id":"BnCicQdHSdxaCv8Ya6Vm","current_title":"Dialogflow CX"},{"title":"Vertex Gemini API","id":"Z0FZJAMvEB4j3NbCJs6B","current_title":"Gemini on Agent Platform"},{"title":"Google Cloud Support","id":"bGThzF7oEGP5jcuDdMuk","current_title":"Google Cloud Support"}],"uri":"incidents/41E5S3mkTGDfkZuJZH5k","currently_affected_locations":[],"previously_affected_locations":[{"title":"Global","id":"global"},{"title":"Montréal (northamerica-northeast1)","id":"northamerica-northeast1"},{"title":"São Paulo (southamerica-east1)","id":"southamerica-east1"},{"title":"Iowa (us-central1)","id":"us-central1"},{"title":"South Carolina (us-east1)","id":"us-east1"},{"title":"Northern Virginia (us-east4)","id":"us-east4"},{"title":"Columbus (us-east5)","id":"us-east5"},{"title":"Oregon (us-west1)","id":"us-west1"}]}]